Beckett R7184 Series 5 Buletin Teknis - Halaman 2
Jelajahi secara online atau unduh pdf Buletin Teknis untuk Pengontrol Beckett R7184 Series 5. Beckett R7184 Series 5 2 halaman. New features in the beckett r7184 series 5 primary controls
Beckett burners have taken advantage of the changes in the R7184 controls to improve the wiring
system. Component and power cord wires, now color-coded to match the terminal colors on the
control, are terminated with 0.25-inch flag terminals (QCs) to fit the spade connectors (QCs) on the
control. During the time required to convert all components and controls to the new wiring system,
some adaptations may be required when replacing individual components on the burner.
CHANGING COMPONENTS — When changing components, the type of connection that you need
to make depends on the way the components (motor, valve, igniter), power cord and control are
terminated. Where all the leads / connections are the same, no modifications are required. Where
the two ends of a connection are dissimilar, see the options in the following table:
If your components are
terminated like this:
Components
Control
Stripped end
Wire leads
Flag terminal
Spade
Flag Terminal
Wire leads
Stripped end
Spade
Fig. 1 – Cutting lead from component to be
replaced to use as jumper
Beckett Service Kits for termination conversion:
51947– Full service kit including a full complement of (6) QC pigtails (BLK, W, O, BLU, V, R), (6) wire
nuts and (9) 0.25-inch flag terminals, and this instruction sheet.
51948– Termination kit including (9) 0.25-inch flag terminals, (6) wire nuts, and instruction sheet.
If you have any questions regarding controls or the Beckett R7184 primary control by Honeywell,
please contact R.W. Beckett at 1-800-645-2876 or visit our web site at www.beckettcorp.com.
R.W. Beckett Corporation • P. O. Box 1289 • Elyria, Ohio 44036 • (800) 645-2876 • (440) 327-1060 • FAX (440) 327-1064
R.W. Beckett Canada Ltd. • Unit 3 - 430 Laird Road • Guelph, Ontario, Canada N1G 3X7 • (800) 665-6972 • FAX (519) 763-5656
RWB 664857R0404
WIRING SYSTEM CHANGES
You should use the following:
Connection options
• Wire nuts
• QC (Quick Connect)
• Cut flag terminal and strip
end– Wire nut
• Add flag terminal to component
lead– QC
• Cut existing component lead 6 -7
in. from flag terminal and strip
end– Wire nut (Fig. 1 & 2)
Reduced number of leads in wiring box.
Fig. 2 – Using jumper to connect to new
component with stripped leads