For required to deflection
Belt section
Small pulley
diameter (mm)
SPA
109 to133
SPA
The belt which is too tight or too loose may generate noise
and be harmful to the unit.
1) Maintenance of fan :
One week after the unit is running, the elastic belt should be
re-adjusted, and should be inspected once every three months in
accordance with the requirements of inspection.
2) Maintenance of belt and pulley :
When the unit is running, check tension of the belt in a regular
time. Do the inspection job according to requirements of inspection
Tension adjustment of the belt: If the belt tension is proper, it will
help to avoid fan vibration, reduce noise and belt abrasion.
Customers should check belt tension every week and do
adjustment according to the following procedures if necessary:
a. Loosen the 4 fixed nuts of motor. Tighten or loosen the nuts
to move the motor.
b. Act in the middle of the belt perpendicularly with a finger.
Adjust belt tension until there's deflection distance, please refer to
Fig 10-4 If possible, it is better to use a tension frequency test
device, in order to get a more precise tension.
c. Tighten the fixed bolt of motor again.
Pulley revise: Fan pulley and motor pulley should on the same
plane, or it will consume much more energy and curtail service
life of belt. Every time after belt adjustment, you should check if
positions of the 2 pulleys are correct, refer to figure 10-3, you can
put a ruler on the same side of 2 pulleys to check if positions of 2
pulleys are correct. Check if point 1, point 2, point 3 and point 4
are in the same plane. If not, you can loosen fixed screws of fan
pulleys and along the fan axle to slide fan pulleys. Loosen motor
to adjust the angle on the fan slide way. Adjust to straightness
2mm.
Installation Manual
14
Newton(N)
Kilogram-force(kgf)
25 to 35
2.5 to 3.6
NOTE
3) When the unit is not running and heating system is not run-time in
the winter, the water must be drained out the coil (system) or add
the appropriate concentration antifreeze, otherwise the coil will be
frost crack.
4) Filter should be cleaned by using water or detergents depending
on the degree of dirt, cleaning frequency according to the using
environment, it is recommended a regular once a month.
5) For the units with humidifier, ECSE etc. special functions, pay
attention to read the components operation instructions along with
the unit, and do periodic check as the instructions.
NOTE
1. Straightness requirements and tension requirements should be
satisfied at the same time after adjusting belt and pulleys.
2. When the service time has reached to 24 hours for the newly used
belt, you must check belt tension and adjust it properly. Improper
adjustment or no adjustment may result in belt lifespan reduction.
Even more it will cause belt fracture.
3. Belt is consumable. It is normal when after 6-months usage, the
belt is abraded and lose efficacy. You need to change a new belt at
this time. If multi-belts rotate, you should change the group of belts
simultaneously.
Replace the air filter.
Loose filter access panel's pole and remove it.
pull out the filter along the supporting slot.
Clean the air filter (Vacuum cleaner or fresh water may be
used to clean the air filter. If the dust accumulated too much,
please use soft brush and mild detergent to clean and dry out
in cool place) .
The air-in side should face up when using vacuum cleaner.
The air-in side should face down when using water.
CAUTION
Do not dry out the air filter under direct sunshine or heat.
Fig.10-6