Juga untuk Daikin R32 Split Series: Panduan Instalasi (17 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (17 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (14 halaman), Panduan Instalasi (14 halaman), Panduan Pengoperasian (16 halaman), Panduan Pengoperasian (16 halaman), Panduan Pengoperasian (8 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (14 halaman), Panduan Instalasi (14 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (17 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (13 halaman)

Daikin R32 Split Series Panduan Instalasi
4 Unit installation
4.1
Preparing the installation site
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (e.g. open flames, an operating
gas appliance, or an operating electric heater). The room
size shall be as specified in the General safety precaution.
4.1.1
Installation site requirements of the
outdoor unit
Mind the following spacing guidelines:
b
>100
a
>50
b
>150
a
>50
(mm)
a
Air outlet
b
Air inlet
NOTICE
The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.
Do NOT install the unit in sound sensitive areas (e.g. near a
bedroom), so that the operation noise will cause no trouble.
Note: If the sound is measured under actual installation conditions,
the measured value might be higher than the sound pressure level
mentioned in "Sound spectrum" in the data book due to
environmental noise and sound reflections.
INFORMATION
The sound pressure level is less than 70 dBA.
The outdoor unit is designed for outdoor installation only and for
ambient temperatures specified in the table below (unless otherwise
specified in the operation manual of the connected indoor unit).
Cooling
–10~50°C DB
4.1.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
Installation manual
6
a
>150
b
>50
b
>100
a
It is recommended to provide at least 150  mm of free space below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
a
>100
level of snow. If necessary, construct a pedestal. See
the outdoor
In heavy snowfall areas it is very important to select an installation
b
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
4.2
4.2.1
Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.
Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field
supply).
Heating
–20~24°C DB
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
unit" [ 4  6] for more details.

Mounting the outdoor unit

To provide the installation structure
a
c
b
"4.2 Mounting
RXJ20~35A
R32 split series
3P482320-17X – 2021.12