Daintree GE Current WA100-PM Panduan Instalasi - Halaman 17

Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Adaptor Daintree GE Current WA100-PM. Daintree GE Current WA100-PM 19 halaman. Wireless adapter

Daintree GE Current WA100-PM Panduan Instalasi
Daintree
Networked Wireless Adapter (WA100-PM)
®
15
Plug Load Applications Continued
Wiring for Combination Plug Load (Aux Relay with
Input Control Signal) and Dimming Light
In the wiring diagram below, the WA100-PM is used to
control both a dimming light and a plug load circuit.
DIP Switches
Driver:
On/Off + 0-10V
On
dimming. Plug
1 2 3 4 5 6
Load On/Off
(#2,3 On)
Perform Installation Test Suite 1
* 0-10V Dimming output, 5 mA available, Up to 10 LED drivers or
fluorescent ballasts typical; the chance of noise on the signal
increases with more.
** Relays used to control plug loads must be compliant with UL498
(Attachment Plug and Receptacles) or equivalant.
17
Installation Guide
Wired Sensor:
None
OFF
ON