DSC PowerSeries PC1616 Panduan Instalasi - Halaman 11

Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Sistem Keamanan DSC PowerSeries PC1616. DSC PowerSeries PC1616 17 halaman. System enhancement module
Juga untuk DSC PowerSeries PC1616: Panduan Instalasi (13 halaman), Panduan Cepat (4 halaman), Panduan Instalasi (20 halaman), Manual (18 halaman)

DSC PowerSeries PC1616 Panduan Instalasi
[005] System Times
This section programs the entry and exit delays for the control panel.
After entering section [005] press [1] to select partition 1.
Enter the 3-digit delay time for Delay 1 type zones, Delay 2 type zones
followed by the exit delay time. Press [#] to exit the sub-menu and
return to regular programming.
NOTE: For SIA FAR Installations, the Exit Delay must be within the
range of 045-255 seconds (Default 60 seconds). If the Exit Delay is
silent (Section 14, Option 6 or Stay Function Key Arming) the exit
delay must be twice the programmed value but must not exceed 255
seconds (i.e., 090-255 seconds).
NOTE: For UL Installations, the Entry Delay plus the Communications
Delay must not exceed 60 seconds.
NOTE: Exit Time Restart shall be disabled when the panel is used in
combination with T-Link TL250/TL300.
[005]
[01] Partition 1 Entry/Exit Times
Def
Enter 3 digits [[001]-[255]
030 I___II___II___I
Entry Delay 1
*045 I___II___II___I
Entry Delay 2
**120 I___II___II___I
Exit Delay 1
*Entry Delay 2 Default is 030 for SIA CP-01 Installations
**Exit Delay 1 Default is 060 for SIA CP-01 Installations
[006] Installer Code
Enter a new 6-digit Installer Code
Default 555555
I___II___II___II___II___II___I
[007] Master Code
Enter a new 6-digit Master Code
Default 123456
I___II___II___II___II___II___I
[008] Maintenance Code
Enter a new 6-digit Maintenance Code
Default AAAAAA
I___II___II___II___II___II___I
[009-010] PGM Programming
PGMs 3&4 apply to PC1864 only
[009]
Main Board PGM Output Programming
Def
Enter 2 digits [[01]-[32]
19
I___II___I
PGM 1
10
I___II___I
PGM 2
01
I___II___I
PGM 3
01
I___II___I
PGM 4
01 Fire & Burglary Output
02 Not Used
03 Sensor Reset (,72)
04 2-Wire Smoke (PGM2 Only)
05 Armed Status)
06 Ready to Arm
07 Keypad buzzer follow mode
08 Courtesy Pulse
09 System Trouble output (with Trouble
Options)
10 System Event (with Event Options)
11 System Tamper (All Sources)
12 TLM and Alarm
13 Kiss-off Output
14 Ground Start Pulse
15 Remote Operation
16 Future Use
Valid entries: [030] to [255]
Valid entries: [030] to [255]
Valid entries: [060] to [255]
Section [009]
Section [009]
Section [010] ...... PC1864 Only
Section [010] ...... PC1864 Only
17 Away Armed Status
18 Stay Armed Status
19 Command Output#1 (,71)
20 Command Output#1 (,72)
21 Command Output#1 (,73)
22 Command Output#1 (,74)
23 24-hr Silent Input
24 24-hr Audible Alarm
25 Delayed Fire & Burglary Output
26 Battery Test Output
27 Police Code Output
28 Holdup Output
29 Zone Follower Inverted Output
30Partition Status Alarm Memory
Output
31 Alternate Communications
32 Open After Alarm (Abort Code)
[013] – First System Option Code
The first two toggle options in this section are used to determine what
type of EOL resistors are being used, toggle option [1] to determine if
normally-closed or EOL resistors are being used and option [2] to
determine if single or double EOL resistors are being used. Configure
the options as required and press [#] to exit
Opt
Default
Description
1
I__I
ON
Normally Closed loops
OFF
End-of-line Resistors
2
I__I
ON
Double End-of-Line Resistors
OFF
Single End-of-Line Resistors
8
I__I
ON
Temporal Three Fire Signal
OFF
Standard Pulsed Fire Signal.
[015] – Third System Option Code
This section is used to determine if the Panic keys on the keypads will
be audible or silent (toggle option [2]) and if phone line supervision is
enabled or disabled (toggle option [7]). Configure the options as
required and press [#] to exit.
Opt
Default
Description
2
I__I
ON
[P] Key Audible (Bell/Beeps) loops
OFF
[P] Key Silent
7
I__I
ON
TLM Enabled
OFF
TLM Disabled
[018] Cross Zone/Police Code
NOTE: The panel uses the cross zoning attribute for Burglary Verifica-
tion. This feature requires two or more trips on a zone(s) specified as
'cross zones' within a specified time before starting an alarm sequence
(See Section[101] Option 3, page 33 of the Reference Manual).
Opt
Default
Description
6
I__I
ON
Cross Zoning Enabled
OFF
Police Code is Enabled
[165] Maximum Dialing Attempts to each Phone Number
This section programs the number of Dialing Attempts. Enter a
3-digit. For UL Listed Installations 5-10 Dialing attempts are
required.
[165]
Maximum Dialing Attempts to each Phone
Def
Enter 3 digits [[001]-[005]
005
I___II___II___I
Valid entries: [001] to [005]
[301] First Telephone Number (32-digits)
Program the central station phone number or CAA for T-LINK.
In addition to the standard digits [0] - [9], Hex digits may also be
required (Refer to the "Programming Decimal and Hexadecimal (HEX)
Data" at the beginning of this section).
D
I
II___II___II___II___II___II___II___II___II___II___II___II___II___II___II___I
I___II___II___II___II___II___II___II___II___II___II___II___II___II___II___II___
[304] Call Waiting Cancel String (6 Digits)
Program Unused digits with Hex F
Default DB70EF [Hex]
I___II___II___II___II___II___I
.