4
TERMINAL DESCRIPTION
PIN
DESCRIPTION
No
1
DC Plant Supply Input
(-ve)
2
DC Plant Supply Input
(+ve)
Fuel relay Output
3
4
Start relay Output
5
Auxiliary Output relay 1
6
Auxiliary Output relay 2
Charge Fail Input/ Excitation
7
Output
8
Low Oil Pressure Input
9
High Engine Temp Input
10
Auxiliary Input 1
Auxiliary Input 2
11
12
Remote Start Input
13
Mains loading Relay
Normally Open contact
14
Generator loading Relay
Normally Open contact
15
Functional Earth
16
Mains L1
Voltage Monitoring Input
17
Mains L2
Voltage Monitoring Input
18
Mains L3
Voltage Monitoring Input
19
Mains N
Voltage Monitoring Input
20
Alternator Input L1
21
Alternator Input N
NOTE:- For single phase mains monitoring the neutral should be connected to terminal
19, L1 should be connected to terminals 16,17 and 18.
NOTE:- For two phase mains monitoring the L2 should be connected to terminal 19, L1
should be connected to terminals 16,17 and 18. The voltage between the two phases must
not exceed 305 Volts.
NOTE:- All the outputs are solid state, rated at 1.2 Amps 8 Volts to 35 Volts DC, and
switch to battery negative when active.
- 12 -
057-042 704 Operating Instructions Issue 2.1 18/06/2007 11:27:00 JR
CABLE
SIZE
1.0mm
Connected to plant battery negative
1.0mm
Connected to plant battery positive
(Recommended Fuse 2A)
Used to operate the fuel relay.
1.0mm
1.0mm
Used to operate the cranking relay.
1.0mm
Configurable output.
1.0mm
Configurable output.
Must NOT be connected to plant supply
1.0mm
negative if not used.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
Switch to negative.
0.5mm
0.5mm
Switch to negative.
1.0mm
Used to close the mains
contactor / breaker
1.0mm
Used to close the generator
contactor / breaker
1.0mm
Connect to a good clean earth point
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains N supply (AC)
1.0mm
Do not connect if not used. (2A Fuse)
1.0mm
Do not connect if not used.
NOTES