Valve Positioner/Actuator/Controller, Field Rangeable
Control Input:
0-50 mV to 0-10 VDC, 0-1 mA to 0-20 mA, 4-20 mA
Output:
8 A SPDT Relay with Neutral Position
O Automatic or Manual Valve Control
O Test/Manual Positioning Buttons
O Input LoopTracker
®
LED
O Relay Status LEDs
O High Capacity Relay Contacts
O One Minute Field Setup
O Removable Plugs for Faster Installation
O Input/Power Isolation
Applications
Q Valve Position Controller
Q Linear Actuator Controller
Q Damper Controller
Control Input
Minimum Span
Maximum Span
Voltage:
0-50 mVDC
0-10 VDC
Current:
0-1 mADC
0-20 mADC
1 VDC maximum burden @ 20 mA
Control Input Impedance
Voltage:
250 kΩ min.
50 Ω typical
Current:
Common Mode Rejection
100 dB minimum
Input Calibration
Multi-turn zero and span potentiometers
±10% of span adjustment range typical
Loop Power Supply
15 VDC ±10%, 25 mA max. to power external loads such as
loop powered transmitters, sensors, etc.
Feedback Potentiometer Range
Any full range potentiometer 0-100 Ω to 0-100 kΩ
Potentiometer excitation: 1.0 VDC nominal, 10 mA maximum
Manual Controls
Automatic/manual switch
Manual open and close buttons
LoopTracker
Variable brightness LEDs for input level and status
Relay Output
SPDT relay with neutral contact position
8 A max @ 240 VAC resistive load
An RC snubber is recommended for inductive loads
AC inductive load
AC resistive
(cos f = 0.4)
8
5
3
DC inductive load
1
(L/R = 7 ms)
0.5
DC resistive
0.3
load
0.1
0
3 5 10
30 50 100 300 500
Switching Voltage (V)
Deadband
12 turn potentiometer adjustable from 1 to 25% of span
Response Time
100 milliseconds nominal
Isolation
Power to input isolation
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
A
A
P
P
BSOLUTE
BSOLUTE
ROCESS
ROCESS
File E145968
85-265 VAC, 60-300 VDC
model only
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Applications Link
api-usa.com/apps
Free Factory
I/O Setup!
1
Minute
Setup!
Dimensions
0.89" W x 4.62" H x 4.81" D
22.5 mm W x 117 mm H x 122 mm D
Height includes connectors
Description
The APD 3280 controls the position of a valve or linear actuator
by comparing a DC input (control signal) to that of a position
feedback potentiometer or slidewire.
load
An SPDT relay provides bi-directional (open-close) signals to
drive a motor to open or close a valve. A bi-color LED indicates
the Open/Close relay contact status.
When the valve position, as indicated by the feedback poten-
tiometer, becomes equal to the position as represented by the
control input, the relay will go to the neutral position and the
motor will halt. A multi-turn deadband control allows precise
tuning of the motor response to eliminate hunting or oscillation.
Heavy-duty relay contacts allow the module to directly control
high capacity loads as long as the switching current with within
the limits shown at left.
How to Order
Models are field rangeable. Switches can pre-set to your
specifications. See range table on other side.
Any full range feedback potentiometer or slidewire from
0-100 Ω to 0-100 kΩ can be used, no need to specify range.
Order APD 3280 D for operation on low voltage power.
Please Specify
Model
Control input range (if factory is to pre-set switches)
Options as required
I
I
NSTRUMENTS
NSTRUMENTS
Position Feedback:
8 A max Relay
Output with
Neutral Position
Potentiometer or
Slidewire Feedback
Zero and Span for
Input
Relay Status LED
Adjustable Relay
Deadband
Input LoopTracker
LED
Auto/Manual Switch
Manual Open/Close
Buttons
24 Switch Selectable
Input Ranges
9 10 11 12
Connect Sink or
Source mA Input
Universal Power
Pb
Lead
Free
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Potentiometer
Quick Link:
1 2 3 4
5 6 7 8
13 14 15 16
See API 3200 G or
APD 3200 for 4-20 mA
or Voltage Feedback
Auto/Manual Switch
An Auto/Manual switch allows either closed-loop automatic
valve position control or manual positioning via the Open/
Close buttons.
The manual mode is useful for troubleshooting, calibration,
system testing or as a manual bypass.
LoopTracker
A green LoopTracker LED varies in intensity with changes in
the control input signal. Monitoring this LED can provide a
quick visual picture of your process at all times and save time
during initial startup and/or troubleshooting.
Model
Description
APD 3280
Field configurable valve
positioner for potentiometer
or slidewire feedback.
APD 3280 D
8 A max. SPDT relay output
Options and Accessories
Optional—add to end of model number
Conformal coating for moisture resistance
U
Accessory—order as separate line item
API BP4
Spare removable 4 terminal plug, black
api-usa.com
Fax: 800-949-7502
APD 3280
api-usa.com/3280
Removable Plugs
See Wiring
Diagrams on
Next Page
Power
60-265 VAC or
85-300 VDC
9-30 VDC or