Auber SYL-2352 Buku Petunjuk - Halaman 2

Jelajahi secara online atau unduh pdf Buku Petunjuk untuk Pengontrol Auber SYL-2352. Auber SYL-2352 8 halaman. Temperature controller

AUBER INSTRUMENTS
3.3 Control output connection
The relay output of the controller SYL-2342 can be used to turn on a contactor
or a solenoid valve. It can drive a small heater directly if the heater draws less
than 10A when connected to 120V AC power source. For applications needing
two control outputs, such as one for heating and another for cooling, relays
AL1 or AL2 can be used for the second output with on/off control mode. Please
see Figure 11 for details.
3.3.1 Connecting the load through a contactor
Assuming the controller is powered by 120V AC and the contactor has a 120V
AC coil, jump a wire between terminals 8 and 9. Connect terminal 7 to one lead
of the coil and terminal 10 to the other lead of the coil. Please see Figure 7 for
example.
3.3.2 Connecting the heater (or cooler) directly from the internal relay
Assuming the controller and the load (heater or cooler) are powered by the
same voltage. Jump a wire from terminal 9 to 8. Connect terminal 7 to the one
lead of the load and terminal 10 to the other lead of the load. Please see Figure
6 and 9 for details.
3.4 For first time users without prior experience with PID controllers, the
following notes may prevent you from making common mistakes.
3.4.1 Power to the heater does not flow through terminal 9 and 10 of the
controller. The controller consumes less than 2 watts of power. It only provides
a control signal to the relay. Therefore, wires in the 18 to 26 gauge range
should be used for providing power to terminals 9 and 10. Thicker wires may
be more difficult to install.
3.4.2 The control relay outputs (for SYL-2342), AL1 and AL2, are "dry" single
pole switches. They do not provide power by themselves. Please see Figure 6,
7 and 11 for how they are wired when providing a 120V output (or when output
voltage is the same as the power source for the controller). If the load of the
relay requires a different voltage than that for the controller, another power
source will be needed. See Figure 8 for examples.
3.4.3 For all controller models listed in this manual, the power is controlled by
regulating the duration of on time for a fixed period of time. It is not controlled
by regulating amplitude of the voltage or current. This is often referred as time
proportional control. For example, if the cycle rate is set for 100 seconds, a 60%
output means controller will switch on the power for 60 seconds and off for 40
seconds (60/100 = 60%). Almost all high power control systems use time
proportional control because amplitude proportional control is too expensive
and inefficient.
4. Front Panel and Operation
3
4
5
6
Figure 2. Front panel
① PV display: Indicates the sensor read out, or process value (PV).
② SV display: Indicates the set value (SV) or output value (%).
③ AL1 indicator: It lights up when AL1 relay is on.
④ AL2 indicator: It lights up when AL2 relay is on.
⑤ A-M indicator: The light indicates that the controller is in manual mode. For
the controllers with the Ramp/Soak option, this light indicates that the
program is running.
⑥ Output indicator: It is synchronized with control output (terminal 7 and 8),
and the power to the load. When it is on, the heater (or cooler) is powered.
2016.05
8 8 8 8
1
8 8 8 8
2
7
8
9
10
⑦ SET key: When it is pressed momentarily, the controller will switch the
lower (SV) display between set value and percentage of output. When
pressed and held for two seconds will put the controller into parameter
setting mode.
⑧ Automatic/Manual function key (A/M) /Data shift key.
⑨ Decrement key ▼: Decreases numeric value of the setting value.
⑩ Increment key ▲: Increases numeric value of the setting value.
4.1 Display Status
SET
SET
SET
A/M
2S
SET
Figure 3. Display modes
Display mode 1: When the power is turned on, the upper display window
shows the measured value (PV) and the lower window shows the four-digit set
value (SV).
Display mode 2: Press the SET key to change the display status into mode 2.
The upper display window shows the measured value (PV) and the lower
windows shows the output value. This picture shows the output percentage is
60% when in Automatic (PID) control mode. If parameter A-M = 1 (see table 2),
pressing the A/M key will switch the controller between PID and Manual control
mode with the output unchanged. This bumpless transfer allows the controller
to be switched between manual and automatic mode without the output
suddenly 'bumping' to a different value.
Display mode 3: Press the SET key for 2 seconds to enter the display mode 3.
This mode allows users to change the system parameters.
4.2 Basic Operation
4.2.1 Changing set value (SV)
Press the ▼ or ▲ key once, and then release it. The decimal point on the
lower right corner will start to flash. Press the ▼ or ▲ key to change SV until
the desired value is displayed. If the change of SV is large, press the A/M key
to move the flashing decimal point to the desired digit that needs to be
changed. Then press the ▼ or ▲ key to start changing SV from that digit. The
decimal point will stop flashing after no key is pressed for 3 seconds. The
changed SV will be automatically registered without pressing the SET key.
4.2.2 Display change
Press the SET key to change the display mode. The display can be changed
between display modes 1 and 2.
WWW.AUBERINS.COM
A/M
P2/8