AuCom CSXI-037 Panduan Pengguna - Halaman 5
Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Pengontrol AuCom CSXI-037. AuCom CSXI-037 13 halaman.
4
Adjustments
1
2
3
Current Ramp
Current Limit
Motor Trip Class
Motor Full Load Current
710-02408-00H
4
5
6
0 3 2 4 6 .D
7
8
Select the initial start current (A) and ramp time
(B).
Current ramp starting extends the time soft
starter takes to reach the current limit and is
suitable for generator set supplies, loads requiring
an extended start time or applications with
extreme load variation between starts.
The ramp time does not control the time the
motor will take to reach full speed.
Select the current limit (C).
The current limit is the maximum level of current
the soft starter will deliver to the motor during
the soft start.
Select the trip class for motor overload
protection.
The trip class reflects the maximum time (in
seconds) that the motor can run at locked rotor
current. The Motor Trip Class setting assumes a
locked rotor current of 600%.
Setting the motor trip class to "Off" disables
motor overload protection.
Configure the soft starter to match the motor's
full load current (FLC).
Configure according to the motor's nameplate
current. Divide the motor's FLC by the soft
starter's maximum current rating (on the soft
starter's nameplate label).
Current Ramp
Current Limit
Motor Trip Class
Motor FLC
Soft Stop Time
Excess Start Time
Auxiliary Relay Function
Phase Sequence Protection
CSXi
ADJUSTMENTS
Time
Time
Page 5