[Address Number Setting]
1. Address number writing
- The address number to be set to the terminal is for correspondence to the input/output memory map of the controller.
This address number is the assigned rst position in the AnyWire input/output transmission frame (0 to 255). In the terminal, 16 points
(input or output) or 8 points (input/output mixed) are occupied after this number. In the case of input/output mixed type, the address
numbers for both input and output are the same.
- The address number can be set by one point.Set the address numbers so that the area occupied by the terminal does not exceed the
maximum transfer points.
- Use a dedicated address writer ARW-04 (Ver.04 to 1.01 or higher) or ARW-03 (Ver. 2.10 or higher) to write the address to be set in the terminal.
As for how to operate address writers ARW-04 (Ver.04 to 1.01 or higher) and ARW-03 (Ver. 2.10 or higher), refer to the product manual of the
address writer.
■ How to set
①Connect the AnyWireASLINK master and power supply to the transmission line of
BL296□B-16F□-4A-20 to supply transmission signals and 24V DC.
②Operate the address writer to write address numbers with the address writer directed at the setting
port of the main body (Fig. 2).
(Hold the light receiving and emitting part as close as possible to the setting port.)
Address numbers settable with BL296□B-16F□-4A-20: Input or output
③In the case of writing in WRITE mode, reset the power supply of BL296□B-16F□-4A-20.
Transmission
signal
24V DC*
*
1
Make sure to use a 24V
DC stabilized power
supply for the power
supply to be connected.
CAUTION
2. Settings reading
When reading the address number which was written in the terminal, also use the address writer.
[Installation Method]
■ ADP-W96 (Installation dedicated DIN rail adapter)
A
A
The state in which the installation dedicated
DIN rail adapter is mounted and fixed in the
same direction as the DIN rail.
Red: DP
AnyWireASLINK
master
Black: DN
Green:
1
24V
24V DC*
The factory setting of the terminal is "255," which means no setting.
In this state, the terminal cannot perform an input/output operation.
Cross-section view A-A
41.90
-BL296*B16F*4A20 5/11-
-BL296*B16F*4A20 5/11-
0 to 240
0 to 248
Input/output mixed
Fig. 2
Setting port
(R/W)
(The port cannot
be seen from the
surface.)
White: 0V
1
B
B
41.90
CAUTION
1:24V
BL296SB-16F~
3:0V
1:24V
BL296XB-16F~
3:0V
1:24V
(Output side)
4:OUT
1:24V
BL296PB-16F~
3:0V
1:24V
4:OUT
1:24V
BL296SB-16FS~
3:0V
1:24V
BL296XB-16FS~
3:0V
3:0V
(Output side)
4:OUT
1:24V
BL296PB-16FS~
3:0V
3:0V
4:OUT
Make sure that no short circuit
occurs in the lines above.
Otherwise, a malfunction may occur.
Cross-section view A-A
The state in which the installation dedicated
DIN rail adapter is mounted and fixed in the
same direction as the DIN rail.