Parameter setting

■Alarm bit selection setting
[Equipment parameter 1]
If you set this parameter to "enabled," the number of occupied input points is
increased by one. When the alarm (ALM) indicator lamp lights, the alarm bit
turns ON to indicate the alarm status to the controller.
Alarm detecting conditions are specified by equipment parameters 11, 12 and 14.
Variable
Description
Alarm bit disabled
0
100
Alarm bit enabled
[When disabled]
Offset address
Type
n
n+1
Input 1 point
Input
Input 2 points
Input 1 Input 2
■Input 0 upper limit setting
[Equipment parameter 2]
This parameter is used to set an upper limit value of pressure detection input 0.
For both hysteresis mode and window comparator mode → Refer to equipment
parameter 8.
■B284SB-01-1KPP30, B284SB-02-1KPP30
Variable
Description
0 to 1000
0 to 1000kPa
■B284SB-01-1KNP30, B284SB-02-1KNP30
Variable
Description
0 to 1000
0 to -100kPa
■B284SB-01-1KLP30, B284SB-02-1KLP30
Variable
Description
0 to 1000
-100 to 100kPa
■B284SB-01-1KPLP30, B284SB-02-1KPLP30
Variable
Description
0 to 1000
0 to 100kPa
■Input 0 lower limit setting
[Equipment parameter 3]
This parameter is used to set a lower limit value of pressure detection input 0.
For both hysteresis mode and window comparator mode → Refer to equipment
parameter 8.
■B284SB-01-1KPP30, B284SB-02-1KPP30
Variable
Description
0 to 1000
0 to 1000kPa
■B284SB-01-1KNP30, B284SB-02-1KNP30
Variable
Description
0 to 1000
0 to -100kPa
■B284SB-01-1KLP30, B284SB-02-1KLP30
Variable
Description
0 to 1000
-100 to 100kPa
■B284SB-01-1KPLP30, B284SB-02-1KPLP30
Variable
Description
0 to 1000
0 to 100kPa
*This parameter cannot be set larger than the input 0 upper limit value (equipment parameter 2).
Factory setting: 0
[When enabled]
Offset address
Type
n
n+1
n+2
Input
Alarm
Input 1 point
Input 1 Input 2
Alarm
Input 2 points
Factory setting: 600 (600kPa)
Factory setting: 600 (-60kPa)
Factory setting: 600 (20kPa)
Factory setting: 600 (60kPa)
Factory setting: 400 (400kPa)
Factory setting: 400 (-40kPa)
Factory setting: 400 (-20kPa)
Factory setting: 400 (40kPa)
-B284SB0*1K**P30 9/16-
■Input 1 upper limit setting
[Equipment parameter 4]
This parameter is used to set an upper limit value of pressure detection input 1.
(For input 2 points type only)
For both hysteresis mode and window comparator mode → Refer to equipment
parameter 8.
■B284SB-02-1KPP30
Variable
Description
0 to 1000
0 to 1000kPa
■B284SB-02-1KNP30
Variable
Description
0 to 1000
0 to -100kPa
■B284SB-02-1KLP30
Variable
Description
0 to 1000
-100 to 100kPa
■B284SB-02-1KPLP30
Variable
Description
0 to 1000
0 to 100kPa
■Input 1 lower limit setting
[Equipment parameter 5]
This parameter is used to set a lower limit value of pressure detection input 1.
(For input 2 points type only)
For both hysteresis mode and window comparator mode → Refer to equipment
parameter 8.
■B284SB-02-1KPP30
Variable
Description
0 to 1000
0 to 1000kPa
■B284SB-02-1KNP30
Variable
Description
0 to 1000
0 to -100kPa
■B284SB-02-1KLP30
Variable
Description
0 to 1000
-100 to 100kPa
■B284SB-02-1KPLP30
Variable
Description
0 to 1000
0 to 100kPa
* This parameter cannot be set larger than the input 2 upper limit value (equipment parameter 4).
■Operation mode selection
[Equipment parameter 8]
This parameter is used to set the hysteresis mode and/or window comparator
mode of input 0 and input 1.
*For details, refer to page 11 to 12.
■B284SB-01-1KPP30, B284SB-01-1KNP30, B284SB-01-1KLP30, B284SB-01-1KPLP30
Variable
Description
0
Hysteresis mode
Window comparator mode
1
■B284SB-02-1KPP30, B284SB-02-1KNP30, B284SB-02-1KLP30, B284SB-02-1KPLP30
Variable
0
Input 0: Hysteresis mode, Input 1: Hysteresis mode
Input 0: Window comparator mode, Input 1: Hysteresis mode
1
2
Input 0: Hysteresis mode, Input 1: Window comparator mode
Input 0: Window comparator mode, Input 1: Window comparator mode
3
Factory setting: 600 (600kPa)
Factory setting: 600 (-60kPa)
Factory setting: 600 (20kPa)
Factory setting: 600 (60kPa)
Factory setting: 400 (400kPa)
Factory setting: 400 (-40kPa)
Factory setting: 400 (-20kPa)
Factory setting: 400 (40kPa)
Factory setting: 0
Description
Factory setting: 0