Anywire ASLINKAMP LA-F1011 Panduan Produk - Halaman 5

Jelajahi secara online atau unduh pdf Panduan Produk untuk Penguat Anywire ASLINKAMP LA-F1011. Anywire ASLINKAMP LA-F1011 11 halaman. Fiber amplifier
Juga untuk Anywire ASLINKAMP LA-F1011: Panduan Produk (11 halaman)

[Installation]
The installation and removal methods are the same for both the base
unit and the extension unit.
Base Extension
Hook movable latch A onto the DIN rail.
Push down on xed latch D on the opposite side until you hear a click.
D
[Removal]
Push this product in direction B, removing xed latch D from the DIN rail.
Lift up straight in direction G, lifting and removing the product.
B
D
G
[Installation Location]
- Location where this product is not directly subject to vibration or shock
- Location where this product is not directly exposed to dust
- Location where this product is not directly exposed to a conductor, such as
waste metal or sputter
- Location without condensation
- Location where the atmosphere is free of corrosive gas, ammable gas, and
sulfur
- Location far from high-voltage or high-current cables
- Location far from cables and controllers that generate servo, inverter, or other
high-frequency noise
[Precautions when Using]
If connecting this unit to a transmission line or expanding the base unit with an
extension unit, do so with supply of the transmission signal stopped.
Performing connections while wires are live may cause the unit to detect
chattering as an error upon connection and stop.
If installing vertically, bring the
movable latch below the DIN rail.
Upper side
A
Upper side
A
-L*F1011 5/11-
[Expansion]
The extension unit can be installed as an expansion on the base unit.
Remove the connector cover on the base unit and connect the
extension unit to the built-in expansion connector.
Expansion connector
Extension
Up to 32 units
LA-F1011 can be expanded by up to 31 LB-F1011 units.
The speci cations for the LA-F1011 and LB-F1011 are as follows.
■Consumption current
DP-DN
LA-F1011
Common
LB-F1011
24V-0V
■Number of occupied points
LA-F1011
Common
LB-F1011
A block with the LA-F1011 expanded by 31 LB-F1011 units occupies
32 input points.
Also, the DP-DN consumption current is 60.8mA.
If ber input with 32 optical axes or more is required, install a separate
block.
If only the LA-F1011 and LB-F1011 are connected, a single system
can support up to 128 units.
Remove the connector cover.
(Do not lose the cover.)
Base
1.9mA
25mA
One-point
One-point