General features and warnings
Plastic housing features
• DIN rail mounting complying with EN 60715
• Self extinguishing V0 according to IEC 60695-11-10 and glowing/hot wire test at 960 °C according to IEC 60695-2-12
• Ball test: 125 °C according to IEC 60730-1. Leakage current: ≥ 250 V according to IEC 60112
Other features
• Operating conditions CE: -20T60 / UL: 0T55, 90% RH non-condensing
• Storage conditions: -30T80, 90% RH non-condensing
• To be integrated in Class I and/or II appliances
• Index of protection: IP40 only on the front cover
• Period of electric stress across insulating parts: long
• Suitable for use in environments with degree of pollution 2
• Category of resistance to heat and fire: D
• Immunity against voltage surges: category II
• Software class and structure: class A
Compliance
This product is designed to comply with the following EU standards:
• Low voltage directive LVD 2014/35/EU:
– EN60730-1: 2011 (Automatic electrical control for household and similar use. General requirements)
– EN60730-2-9: 2010 (Particular Requirements for Temperature Sensing Controls)
• Electromagnetic compatibility EMC directive 2014/30/EU:
– EN 61000-6-3: 2007 +A1: 2011 (Emission standard for residential, commercial and light-industrial environments)
– EN 61000-6-2: 2005 (Immunity for industrial environments)
• RoHS directive 2011/65/EU and 2015/863/EU:
– EN50581: 2012
UL approval:
• UL file E31024
General warnings
• Every use that is not described in this manual is considered incorrect and is not authorised by the manufacturer
• Verify that the installation and operating conditions of the device respect the ones specified in the manual, specially concerning the
supply voltage and environmental conditions
• This device contains live electrical components therefore all the service and maintenance operations must be performed by qualified
personnel
• The device can't be used as a safety device
• Liability for injury or damage caused by the incorrect use of the device lies solely with the user
Installation warnings
• Mounting position recommended: vertical
• The installation must be executed according the local standards and legislation of the country
• Always operate on the electrical connections with the device disconnected from the main power supply
• Before carrying out any maintenance operations on the device, disconnect all the electrical connections
• For safety reasons the appliance must be fitted inside an electrical panel with no live parts accessible
• Don't expose the device to continuous water sprays or to relative humidity greater than 90%.
Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of flammable gases are
present, dust, strong vibrations or chock, large and rapid fluctuations in ambient temperature that in combination with high humidity
can condensate, strong magnetic and/or radio interference (e.g. transmitting antennae)
• When connecting loads beware of the maximum current for each relay and connector
• Use cable ends suitable for the corresponding connectors. After tightening the screws of connectors, slightly tug the cables to check
their tightness
• Use appropriate data communication cables. Refer to the Fieldbus Installation Guide for the kind of cable to be used and setup
recommendations
• Reduce the path of the probe and digital inputs cables as much as possible, and avoid spiral paths enclosing power devices. Separate
from inductive loads and power cables to avoid possible electromagnetic noises
• Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges
Disposal instruction
Equipment containing electrical components may not be disposed together with domestic waste. It must be separately collected
with electrical and electronic waste according to local and valid legislation.