Danfoss AB-PM DN 80 Lembar data - Halaman 6

Jelajahi secara online atau unduh pdf Lembar data untuk Pengontrol Danfoss AB-PM DN 80. Danfoss AB-PM DN 80 12 halaman. Pressure difference controller with integrated flow limiter

Data sheet
Sizing graph - ΔP/ max. flow
See datasheet AB-PM
1)
DN 10-32
Sizing
Example 1
Given : Design flow to zone
4200 l/h, pressure drop over
the zone at design flow 25 kPa.
Solution: AB-PM DN 40 is
selected. Δp setting is kept
at factory setting and flow
limitation is changed to 80 %.
AB-PM will control differential
pressure of 25 kPa when
design flow is achieved and
the flow to the zone will be
limited to 4200 l/h
6 | VD.HR.D1.02
AB-PM DN 40-100
55000
50000
45000
40000
35000
30000
25000
20000
15000
10000
5000
AB-PM HP DN 10-32
1)
0
10
15
20
Fig. 5
DN 40
13000
12000
11000
10000
9000
100 %
8000
90 %
80 %
7000
70 %
6000
60 %
5000
50 %
Example 1
40 %
4000
3000
2000
10
15
20
Fig. 6
DN 40
Flow limitation on Δp factory setting
Δp
40%
50%
r
[kPa]
10
4600
5520
15
4000
4800
20
3300
3960
25
2500
3000
30
35
40
45
50
55
60
Table 1
DN 100
DN 80
DN 65
DN 50
DN 40
25
30
35
P
[kPa ]
r
5 turns
10 turns
25
30
35
p
[kPa]
r
60%
70%
80%
90%
Q [l/h]
6348
7084
7728
8280
5520
6160
6720
7200
4554
5082
5544
5940
3450
3850
4200
4500
2070
2310
2520
2700
40
45
50
15 turns
20 turns
40
45
50
Factory
∆p setting [kPa]
setting
100%
/0 turns
5 turns
10 turns 15 turns 20 turns
9200
8000
6600
9200
5000
8000
10200
3000
6600
9200
11100
5000
8000
10200
3000
6600
9200
5000
8000
3150
6600
5000
3150
© Danfoss | 2018.01
55
60
55
60
11900
11100
10200
9200
8000
6600