Danfoss AK-CH 650 Panduan Servis - Halaman 12

Jelajahi secara online atau unduh pdf Panduan Servis untuk Pengontrol Danfoss AK-CH 650. Danfoss AK-CH 650 15 halaman. Capacity controller for water chiller

Danfoss AK-CH 650 Panduan Servis
Request Cond. cap %
Thermostat 1 °C
Thermostat 2 °C
Thermostat 3 °C
Pressostat 1 Bar
Pressostat 2 Bar
Settings
Main switch
Ther. 1 Cutin °C
Ther. 1 Cutout °C
Ther. 1 High Alarm °C
Ther. 1 Low Alarm °C
Ther. 1 High ALDly m
Ther. 1 Low ALDly m
Ther. 2............
Ther. 3............
Pres. 1 Cutin bar
Pres. 1 Cutout bar
Pres. 1 High alarm bar
Pres. 1 Low alarm bar
Pres. 1 High ALDly m
Pres. 1 Low ALDly m
Pres. 2............
(Use Service Tool if data concerning thermostats 4 and 5 or from pressure controls 3, 4 and 5 have to be downloaded).

Voltage inputs

Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
Volt 1 readout
Settings
Main switch
Volt 1 Cutin
Volt 1 Cutout
Volt 1 Cutin del. m
Volt 1 Cutout del. m
Volt 1 High Al.Limit
Volt 1 Low Al.Limit
Volt 1 High Al.Dly m
Volt 1 Low Al.Dly m
(Use Service Tool if data concerning Volt 2, 3, 4 and 5 are to be downloaded).
12
Reference for condenser capacity
Temperature measurement of function defined in Thermostat 1.
Temperature measurement of function defined in Thermostat 2.
Temperature measurement of function defined in Thermostat 3.
Pressure measurement of function defined in Pressure Control 1
As above, but for pressostat 2
Main switch:
Cutin value for function defined in "Thermostat 1".
Cutout value for function defined in "Thermostat 1".
High alarm limit "Thermostat 1"
Low alarm limit "Thermostat 1"
Time delay for high alarm "Thermostat 1"
Time delay for low alarm "Thermostat 1"
As above, but for thermostat 2
As above, but for thermostat 3
Cutin value for function defined in "Pressure Control 1".
Cutout value for function defined in "Pressure Control 1".
High alarm limit "Pressostat 1"
Low alarm limit "Pressostat 1"
Time delay for high alarm "Pressostat 1"
Time delay for low alarm "Pressostat 1"
As above, but for pressostat 2
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Voltage measurement on the function defined in Volt 1.
Main switch:
The value where the relay is to cut in
The value where the relay is to cut out
Time delay for cutin of relay
Time delay for cutout of relay
The value for the high alarm limit
The value for the low alarm limit
Time delay for high alarm
Time delay for low alarm
Service Guide
RC8BV402 © Danfoss 2016-02
ON:
Regulation
OFF: Controller stopped
ON:
Regulation
OFF: Controller stopped
AK-CH 650 Version 2.0x