Air flow status
Sc3 Air on °C
VSD Speed %
VSD safety
Heat rec. temp. °C
Heat recovery
No. of fans
Settings
Main switch
Cap. control mode
Manual capacity %
Reference mode
Setpoint °C
Dimensioning tm K
Min. tm k
Min. Reference °C
Max. Reference °C
Heat rec. SP °C
Heat rec. Cut In °C
Heat rec. CutOut °C
Xp P-band K
Tn Integr. time s
Control type
VSD Min. speed %
VSD Start speed %
Cap. limit night %
AK-CH 650 Version 2.0x
0: No RFG. select No refrigerant has been selected (monitoring of air
1: Tuning
2: OFF
3: OK
4: Little dirt
5: Dirty
6: Blocking
Outdoor temperature in °C measured with Sc3 temperature sensor
Status of analogue output signal "AO" for variable speed drive (in percent of
full scale f.ex. 0 -10 V d.c.)
Status of safety monitoring input for Variable Speed Drive
ON: Alarm on VSD A safety monitoring input
OFF: No alarm on VSD A safety monitoring input
Temperature at the sensor for the heat recovery function
Status on function "Heat recovery"
Defined number of fans
Main switch:
0: MAN (The condenser capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual setting of condenser capacity
The value is in % of total capacity controlled by the controller
0: Set point
1: Floating
Setting of required discharge pressure in °C
Dimensioning mean temperature differential between air- and condensing
temperature at full load for the condenser in question (Typical 8 – 15K).
tm value at minimum load.
Min. permissible condensing pressure reference
Max. permissible condensing pressure reference
Condensing pressure reference when the thermostat for heat recovery is cut in.
Temperature value when the thermostat changes over to heat recovery.
Temperature value when the thermostat cuts out the heat recovery again
Proportional band for PI controller
Integration time for PI controller
Selection of regulation type:
0: P regulation
1: PI regulation
Minimum allowed speed before stop of Variable Speed drive (Low load condition)
Minimum speed for start of Variable speed drive (Must be set higher than
"VSD Min. Speed %")
Capacity limitation during night operation
Service Guide RC8BV402 © Danfoss 2016-02
flow can not start)
Monitoring function adapts to the condenser in question
Monitoring function is switched OFF
Air flow is OK
The amount of dirt decreases the performance of the condenser,
clean when possible
The amount of dirt leads to considerable air flow problems, clean
as soon as possible
The amount of dirt might lead to high pressure problems, clean
now
ON:
Regulation
OFF: Controller stopped
Reference = "PcA setpoint °C"
Reference is changed as a function of the outdoor temperature
measured by the "Sc3 air on" sensor, the set "Dimensioning tm K"
and the actual compressor load.
9