Danfoss VLT HVAC Instruksi - Halaman 5

Jelajahi secara online atau unduh pdf Instruksi untuk Pengontrol Danfoss VLT HVAC. Danfoss VLT HVAC 11 halaman. Cascade controller
Juga untuk Danfoss VLT HVAC: Petunjuk Manual (16 halaman)

Danfoss VLT HVAC Instruksi
VLT® HVAC Basic Drive Casca...
Parameter
Range
25-20 Staging
1 - Expres-
Bandwidth
sionlimit (100)
%
Expressionlimit
(100) - 100%
25-22 Fixed
Expressionlimit
Speed
(1) - Expres-
Bandwidth
sionlimit (100)
%
25-23 SBW
0-3000 s
Staging Delay
25-24 SBW
0-3000 s
Destaging
Delay
25-25 OBW
0-300 s
Time
25-27 Stage
[0] Disabled
Function
*[1] Enabled
25-28 Stage
0-300 s
Function Time
25-29 Destage
[0] Disabled
Function
*[1] Enabled
25-30 Destage
0-300 s
Function Time
®
VLT
HVAC Basic Drive Cascade Controller
Default
Function
*10%
Set the SBW
percentage to
accommodate
system pressure
fluctuation.
*100%
Set the OBW for
when to override
the staging/
destaging timers
for immediate
response.
*Expres-
Set the staging
sionlimit
bandwidth to use
(10)%
when only fixed
speed pumps are
running.
*15 s
Staging a pump
on is delayed by
the length of
time
programmed.
*15 s
Destaging a
pump is delayed
by the length of
time
programmed.
*10 s
OBW timer
prevents staging
a pump until the
system pressure
is stabilised.
*[1] Enabled
Enables the stage
function timer.
*15 s
With the lead
pump at
maximum speed,
a fixed speed
pump is staged
on when the
programmed
time expires.
*[1] Enabled
Enables the
destage function
timer.
*15 s
With the lead
pump at
minimum speed,
a fixed speed
pump is
destaged when
the programmed
time expires.
®
MI18I302 - VLT
is a registered Danfoss trademark
Parameter
Range
25-42 Staging
Expressionlimit
Threshold
(0)-100%
25-43 Destagi
Expressionlimit
ng Threshold
(0)-100%
25-45 Staging
0-400 Hz
Speed [Hz]
25-47 Destagi
0-400 Hz
ng Speed [Hz]
25-50 Lead
*[0] Off
Pump
[1] At staging
Alternation
[2] At
command
[3] At staging
or command
25-51 Alternati
*[0] External
on Event
[1] Alternation
Time Interval
[2] Sleep Mode
25-52 Alternati
1-999
on Time
Interval
25-53 Alternati
on Timer
Value
25-55 Alternat
[0] Disabled
e if Load <=
*[1] Enabled
50%
25-56 Staging
*[0] Slow
Mode at
[1] Quick
Alternation
25-57 Relays
1-2
per Pump
Default
Function
*90%
The percentage
[%] of maximum
pump speed to
stage on a fixed
speed pump.
*50%
The percentage
[%] of maximum
pump speed to
destage a fixed
speed pump.
*0.0 Hz
The actual
staging speed
based on the
staging threshold.
*0.0 Hz
The actual
destaging speed
based on the
destaging
threshold.
*[0] Off
Changes the lead
pump so all
pumps run equal
time.
*[0] External
Choose the event
that will change
the lead pump.
*24
Set the time
period between
automatic
alternation of the
lead pump.
View the actual
value of the
Alternation Time
Interval timer.
*[1] Enabled
Choose enable to
change the
variable speed
pump only if the
pump load is less
than 50%.
*[0] Slow
*1
The number of
relays used per
pump.
3
1
1