Danfoss VLT Soft Starter MCD 600 Panduan Instalasi - Halaman 6
Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Pengontrol Danfoss VLT Soft Starter MCD 600. Danfoss VLT Soft Starter MCD 600 20 halaman. Modbus rtu card
Juga untuk Danfoss VLT Soft Starter MCD 600: Panduan Instalasi (2 halaman), Panduan Instalasi (20 halaman)
Installation Guide | DeviceNet Card
Example:
5
4
3
2
1
Illustration 2:
5-way Connector Plug
Pin
5
4
3
2
1
Network designs must decrease the maximum allowable cumulative dropline length for every device installed on the network.
Failure to do so may result in network communication errors and decreased reliability.
Decrease the maximum allowable cumulative dropline by 400 mm per device in the network.
-
Example:
ODVA specifies a maximum cumulative dropline length of 156 m on a network operating at 125 kb/s. If 6 devices were installed on this
network, the total dropline length would need to be decreased to 153.6 m.
2.3 Feedback LEDs
2.3.1 Module and Network LEDs
The Module LED indicates the condition of the power supply and device operation.
The Network LED indicates the status of the communication link between the device and the network Master.
6 | Danfoss A/S © 2018.10
Function
V+
CAN_H
SHIELD
CAN_L
V-
N O T I C E
Installation
AQ277154750780en-000102 / 175R1182