Danfoss KP 62 Petunjuk - Halaman 3
Jelajahi secara online atau unduh pdf Petunjuk untuk Termostat Danfoss KP 62. Danfoss KP 62 4 halaman. Vapour charge, adsorption charge (cross ambient)
Juga untuk Danfoss KP 62: Panduan Instalasi (2 halaman), Panduan Instalasi (4 halaman)
Adjustment spindles location
Note!
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
See printed instruction on top of control
increase temp. (warmer): turn CW
decrease temp. (colder): turn CCW
(use adjustment knob)
Determination of diff erential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct diff erential
Example:
HSP = +45°F (+5.6°C)
=>
LSP = +32°F (0°C
© Danfoss A/S
DIFF (from graph):
13°F (7.2°C) (value which has to be
set on diff . scale).
RI.5D.A2.22 → DKRCC.PI.C0A.A1.22-520H2749
DIFFERENTIAL
See printed instruction on top of control
Increase: turn CW
decrease: turn CCW
(use adjustment knob or screwdriver)
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The diff erential will be HSP less LSP
Example:
HSP – LSP = DIFF.
45°F – 35°F = 10°F
(7°C)
(5°C)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
CUT-OUT = LSP
CUT-OUT = HSP
See "Wiring"
(2°C)
= LSP
3