Betriebs- und Montagean-
leitung
Luftdruckwächter
LGW...A2 SGN
EN 1854
HR
SRB
7 – 150 mbar
2,5 – 50 mbar
2 – 10 mbar
0,4 –
3 mbar
[mbar]
5 ... 16
Operation and assembly
instructions
Air pressure switch
LGW...A2 SGN
Druckwächter / Pressure Switch/
Pressostat/Pressostato
Typ/Type/Type/Tipo
LGW...A2 SGN
nach/acc./selon/a norme
DIN EN 1854
TÜV-geprüfte Komponenten
für Biogasanlagen gemäß TÜV-
Arbeitsanweisung IS-TAF 411.
MRZ.-2007. Für Bio- und Klär-
gase nach DVGW Arbeitsblatt
G 262.
TÜV-inspected components for
biogas installations according
to TÜV work instruction IS-TAF
411.MRZ.-2007. For biogases
and sewage gases according to
DVGW worksheet G 262.
Composants contrôlés TÜV pour
installations à biogaz conformé-
BIH
SK
ment aux instructions de travail
TÜV (IS-TAF 411.MRZ.-2007):
Pour les biogaz et le gaz de
curage selon la fiche technique
DVGW G 262 Union allemande
des techniques de l'eau et du
gaz).
C o m p o n e n t i
c o n t r o l l a t i
dall'ufficio tedesco per la sor-
veglianza tecnica TÜV per impi-
anti di biogas in conformità alle
istruzioni di lavoro TÜV IS-TAF
411.MRZ.-2007. Per biogas e gas
di digestione in conformità al
foglio di lavoro dell'associazione
tedesca dei settori gas e acqua
DVGW G 262.
Einstellbereiche
Setting ranges
Plages de réglage
Campi di taratura
Max. Betriebsdruck / Max. operating
pressure/ Pression de service maxi.
Max. pressione di esercizio
p
= 500 mbar (50 kPa)
max.
Notice d´emploi et de
montage
Pressostat air
LGW...A2 SGN
Au
[V]
Au
[A]
EN 1854
IEC 529
IEC 529
Istruzioni di esercizio e di
montaggio
Pressostato per aria
LGW...A2 SGN
Standard Anwendung/Standard
application/Application stan-
dard/Applicatione standard
~(AC) eff., min./mini 24 V,
~(AC) max. /maxi. 250 V
=(DC) min./mini. 24 V,
=(DC) max. /maxi. 48 V
DDC-Anwendung/DDC applica-
tion/application DDC/Applica-
zione DDC
=(DC) min./mini. 5 V,
=(DC) max. /maxi. 24 V
Standard Anwendung/Standard
application/Application stan-
dard/Applicatione standard
Nennstrom/nominal current/cou-
rant nominal/corrente nominale
~(AC) 10 A
Schaltstrom/current on contact/
courant de commutation/cor-
rente di intervento
~(AC) eff., min./mini 20 mA,
~(AC) max./maxi. 6 A cos ϕ 1
~(AC) max./maxi. 3 A cos ϕ 0,6
=(DC) min./mini. 20 mA
=(DC) max./maxi. 1 A
DDC-Anwendung/DDC applica-
tion/application DDC/Applica-
zione DDC
Nennstrom/nominal current/cou-
rant nominal/corrente nominale
=(DC) 20 mA
Schaltstrom/current on contact/
courant de commutation/cor-
rente di intervento
=(DC) min./mini. 5 mA
=(DC) max./maxi. 20 mA
ACHTUNG / ATTENTION
ATTENTION / ATTENZIONE
Nach Anwendung (> 24 V / > 20 mA)
ist eine spätere DDC-Anwendung
nicht mehr möglich.
After application (> 24 V / > 20 mA),
a later DDC application is no
longer possible.
Après utilisation (> 24 V / > 20 mA),
une utilisation DDC ultérieure
n'est plus possible.
Dopo l'impiego (> 24 V / > 20 mA) non
è più possibile un impiego DDC.
Schutzart / Degree of protection
Protection / Protezione
LGW...A2.. SGN
IP 65 nach / acc. / selon / a norme