Juga untuk Danfoss ECL Comfort 210: Panduan Pengguna (12 halaman), Panduan Pengguna (12 halaman), Panduan Pengguna (6 halaman), Panduan Instalasi (4 halaman), Panduan Instalasi (20 halaman), Panduan Pengoperasian (16 halaman), Panduan Pengoperasian (10 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (16 halaman), Manual Pemasangan (16 halaman)

Danfoss ECL Comfort 210 Panduan Instalasi
Installation Guide

2.2 Differentiated heat cut-out

To set differentiated cut-out parameters for a heating circuit for
"Summer" and "Winter" go to "Heat cut-out":
(MENU > Settings > Heat cut-out)
This function is active when the dates for "Summer" and "Winter"
are different in the "Heat cut-out" menu.
Extended heat cut-out setting
Parameter
ID
11393
Summer day
11392
Summer month
Summer cut-out
11179
Summer filter
11395
Extended winter cut-out setting
Parameter
ID
11397
Winter day
11396
Winter month
Winter cut-out
11398
11399
Winter filter
The above settings of the dates for the cut-out function are only
to be done in the heating circuit 1 and are valid for other heating
circuits in the controller as well, if applicable.
The cut-out temperatures as well as the filter constant are to be set
individually per heating circuit.
Danfoss District Energy
ECL Comfort 210 and 310, extended heat cut-out
Setting range
Factory
setting
1 ... 31
20
1 ... 12
OFF / 1 ... 50°C
20°C
OFF / 1 ... 300
250
Setting range
Factory
setting
1 ... 31
20
1 ... 12
OFF / 1 ... 50°C
20°C
OFF / 1 ... 300
250
5
5
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
VI.GU.U1.02
DEN-SMT/DK
5