Danfoss ECL Comfort 310 Panduan Pengoperasian - Halaman 6

Jelajahi secara online atau unduh pdf Panduan Pengoperasian untuk Unit Kontrol Danfoss ECL Comfort 310. Danfoss ECL Comfort 310 10 halaman. A302
Juga untuk Danfoss ECL Comfort 310: Panduan Instalasi (8 halaman), Manual Pemasangan (4 halaman), Panduan Pengguna (12 halaman), Panduan Pengguna (12 halaman), Panduan Instalasi (4 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Servis (16 halaman), Panduan Pengoperasian (8 halaman), Panduan Pengoperasian (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (7 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (16 halaman), Panduan Instalasi (20 halaman), Panduan Instalasi (12 halaman), Manual Pemasangan (20 halaman), Manual Pemasangan (20 halaman), Manual Pemasangan (12 halaman), Manual Pemasangan (16 halaman), Panduan Pengoperasian (8 halaman)

Danfoss ECL Comfort 310 Panduan Pengoperasian
ECL Comfort 210, 296 and 310, return temperature limitation
MENU > Settings > Return temperature limitation in a master /
slave system
Demand offset
Circuit
1
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
1 ... 20: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
MENU > Settings > Return temperature limitation in a master /
slave system
Send desired T
Circuit
Sub-circuit in the same ECL controller:
Information about the desired flow temperature can be sent to circuit 1.
The ECL controller acts as a slave controller in a master / slave system:
Information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
OFF:
Information about the desired flow temperature is not
sent to circuit 1 / master circuit / the master controller.
ON:
Information about the desired flow temperature is sent
to circuit 1 / master circuit / the master controller.
6 | © Danfoss | 2017.08
11017
Setting range
Factory setting
OFF / 1 ... 20 K
OFF
1x500
Setting range
Factory setting
OFF / ON
Temp.
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
Slave circuits are circuits in other ECL controllers.
Sub-circuits are circuits besides the master or circuit 1 in the ECL
controller.
ON
In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in
order to send the desired temperature to the master (see the section
'Miscellaneous' , 'Several controllers in the same system').
Setting in
'Demand offset'
Des. flow temp.,
circuit 1
Des. flow temp.,
circuit 2
Time
VI.GU.W2.02