Danfoss VLT MCD 200 Panduan Petunjuk Instalasi - Halaman 10

Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Unit Kontrol Danfoss VLT MCD 200. Danfoss VLT MCD 200 17 halaman. Usb module
Juga untuk Danfoss VLT MCD 200: Panduan Petunjuk Instalasi (6 halaman), Petunjuk Instalasi (5 halaman)

Danfoss VLT MCD 200 Panduan Petunjuk Instalasi
AP ASCII Protocol

10.2. Status Retrieval

Soft starter status can be retrieved using the following format:
Request
Trip code
Starter status

10.3. Data Retrieval

Data can be retrieved from the soft starter using the following format:
Request
Motor current
Motor
temperature
ASCII
Receive Status (ssss)
C18
See the trip code table.
C22
Bit
0 to 3
4
5
6
7
ASCII
Receive Data (dddd)
D10
Requests motor current. The data is four byte decimal ASCII. Minimum value
0000 A, maximum value 9999 A.
D12
Requests the calculated value of the motor thermal model as a % of motor
thermal capacity. The data is four byte decimal ASCII. Minimum value is
0000%. Trip point is 0105%.
MG.17.F5.02 - VLT® is a registered Danfoss trademark
Description
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including Temperature check)
6 = Tripped
7 = Program mode
1 = Positive phase rotation (only valid if bit 6 = 1)
1 = Current exceeds FLC
0 = Uninitialised
1 = Initialised
0 = Communications are OK
1 = Communications device fault
MCD Modbus Module Instructions
10