Danfoss RSH Series Panduan Instalasi - Halaman 2

Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Pompa Air Danfoss RSH Series. Danfoss RSH Series 4 halaman. Oil pump
Juga untuk Danfoss RSH Series: Panduan Instalasi (4 halaman)

Danfoss RSH Series Panduan Instalasi
Installation Guide, RSH
DK
Oliepumpe type RSH
Tekniske data
Standard fyringsolie
Olietyper
Viskositetsområde:
- selvansugende
- med fødetryk
Omdrejningstal
Trykområde:
15 - 35 bar (x 10
- med specialfjeder
Fabriksindstilling
Medietemperatur
Max. føde- og returtryk
Tilslutninger (fig. 1)
P = dysetilslutning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
S = sugeledning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
Fødetryksmåling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
R = returledning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
M = trykmåling/udluftning . . . . . . . . . . . . . . . . . . . . G 1/8
Bemærk!
Samtlige tilslutninger har anslået pakflade beregnet
for standardfladepakninger.
Type RSH leveres som 1-strengs pumpe med omløbet
"G" åbent (fig. 4).
Ved 2-strengs drift monteres den medleverede skrue
"A" i omløbet "G" (fig. 5).
Pumperne er selvansugende ved viskositeter op til
20 mm
2
/s. Ved højere visikositeter bør pumpen forsy-
nes med positivt fødetryk.
Ved 1-strengs drift med underliggende tank bør dyse-
ledningen monteres i udluftningsporten "M" og dyse-
porten "P" afblændes. Der skal her anvendes en afskæ-
rings-/lukkeventil på dyseledningen.
Omdrejningsretning
Set fra akselenden har en højregående pumpe om-
drejningsretning med uret, og en venstregående mod
uret.
Udluftning
Ved 1-strengs anlæg udluftes pumpen ved 1-gangs
opstart via udluftningsstudsen "M" (fig. 2).
Ved 2-strengs anlæg udlufter pumpen automatisk
gennem returledningen.
Trykindstilling
Fig. 3 viser trykindstilling af en RSH pumpe. Maks. tryk
er afhængig af trykområde.
1-gangs opstart
Med let fyringsgasolie startes brænderen og pumpen
justeres til det ønskede tryk.
Med svær fyringsolie justeres til min. tryk. Pumpen dre-
jes langsomt til der er varm olie fremme ved trykmå-
lestudsen.
Brænderen startes og pumpen justeres jævnt op til
det ønskede drifttryk.
Samme metode anvendes efter driftstop hvor olien er
blevet helt eller delvis kold.
Efter denne indjustering arbejder pumpen under norma-
le driftsbetingelser.
Anlæg
Installationen skal forsynes med forfilter efter gælden-
de regler/praksis.
Medier
Pumpen er specificeret for drift med mineralske
brændselsolier, henholdsvis medier med tilsvarende
eller højere klassifikation.
2 | © Danfoss | 2019.04
Tilbehør
Til RSH-serien kan der leveres en løs flange incl. 4 skru-
er til montage på halsens anlægsflade.
Bestillingsnummer: 070-0211
og bio olie (FAME)
Oil pump type RSH
Technical data
4,3 - 20 mm
/(cSt)
2
20 - 760 mm
2
/(cSt)
Oil types
1400 - 3450 min
-1
Viscosity range:
2
kPa)
- self-priming
1 - 5 bar (x 10
kPa)
2
- with feed pressure
21 bar (x 10
kPa)
2
Speed
-10 til +120 °C
Pressure range:
4 bar (x 10
kPa)
2
- with special spring
Default settings
Temperature of medium
Max. feed and return pressure
Connections (fig. 1)
P = nozzle connection . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
S = suction connection . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
Feed pressure measurement . . . . . . . . . . . . . . . . . . . G 1/4
R = return line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
M = pressure measurement/bleed . . . . . . . . . . . . . G 1/8
Note!
All connection surfaces are spotfaced for standard
gaskets.
RSH is supplied as a 1-pipe pump with bypass "G"
open (fig. 4).
For 2-pipe operation, screw "A" supplied must be fitted
in bypass "G" (fig. 5).
The pumps are self-priming for viscosities up to 20
mm
2
/s. For higher viscosities, the pump should be con-
nected to positive feed pressure.
For 1-pipe operation with underlying tank, the nozzle
line should be connected to vent port "M", with nozzle
port "P" blanked off. In this case a shut-off valve must
be installed in the nozzle line.
Direction of rotation
The direction of rotation of a righthand pump is clock-
wise, a lefthand pump counterclockwise, when look-
ing on the end of the shaft.
Venting
On 1-pipe operation the pump is vented on first-time
starting via vent port "M" (fig. 2).
On 2-pipe operation the pump is vented automatically
through the return line.
Pressure settings
Fig. 3 shows the pressure setting of an RSH pump.
Max. pressure is dependent on the pressure range.
First-time starting
With light fuel oil, the burner must be started and the
pump adjusted to the required pressure.
With heavy fuel oil the setting must be on minimum
and the pump turned slowly, until hot oil appears at
the pressure measurement connection.
The burner can then be started and the pump adjust-
ed evenly up to the required operating pressure.
The same method must be used after an operational
stop when the oil has become partially or completely
cold.
After this adjustment has been made the pump will
run under normal operating conditions.
Installation
A prefilter must be installed, in accordance with cur-
rent rules/practice.
Media
The pump is specified for operation with mineral-
based fuel oils, or media having a corresponding or
higher classification.
Accessories
GB
A separate flange with four screws for mounting on
the neck of the pump can be supplied for the RSH se-
ries.
Code no. 070-0211
The RSH can be used as a feed/transport pump after
the pressure setting spring has been replaced.
Standard fuel gas oil
A replacement pressure setting spring with a range of
and bio oil (FAME)
1-5 bar (x 102 kPa) together with a label giving the
correct pressure range are obtainable under code
4,3 - 20 mm
/(cSt)
2
number 070-0030.
20 - 760 mm
2
/(cSt)
1400 - 3450 min
-1
15 - 35 bar (x 10
2
kPa)
Ölpumpe Typ RSH
1 - 5 bar (x 10
2
kPa)
21 bar (x 10
kPa)
2
Technische Daten
-10 to +120 °C
Öltypen
4 bar (x 10
kPa)
2
Viskositätsbereich:
- selbstansaugend
- mit Speisedruck
Drehzahl
Druckbereich:
- mit Spezialfeder
Werkseinstellung
Medientemperatur
Max. Speise- und
Rücklaufdruck
Anschluß (Fig. 1)
P = Düsenanschluß . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
S = Saugleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
Speisedruckmessung . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
R = Rücklaufleitung. . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/4
M = Druckmessung/Entlüftung . . . . . . . . . . . . . . . . G 1/8
Achtung!
Sämtliche Anschlüsse haben Dichtflächen für Stan-
dard- Flachdichtungen.
Typ RSH wird als 1-Strang-Pumpe mit offenem Umlauf
"G" geliefert (Fig. 4).
Bei 2-Strang-Betrieb ist die mitgelieferte Schraube "A"
in den Umlauf "G" zu montieren (Fig. 5).
Die Pumpen sind selbstansaugend bei Viskositäten bis
20 mm2/s. Bei höheren Viskositäten ist die Pumpe an
positiven Speisedruck anzuschließen.
Bei 1-Strang-Betrieb mit tieferliegendem Tank muß die
Düsenleitung in die Entlüftungsöffnung "M" montiert
und die Düsenöffnung "P" verschlossen werden. Hier
muß ein Abschneide-/Schließventil an der Düsenlei-
tung angewendet werden.
Drehrichtung
Auf das Wellenende gesehen, läuft eine rechtdrehen-
de Pumpe im Uhrzeigersinn und eine linksdrehende
gegen den Uhrzeigersinn.
Entlüftung
Bei 1-Strang-Anlagen ist die Pumpe bei der erstmali-
gen Inbetriebnahme durch den Entlüftungsstutzen
"M" zu entlüften (Fig. 2).
Bei 2-Strang-Anlagen entlüftet die Pumpe automa-
tisch durch die Rücklaufleitung.
Druckeinstellung
Fig. 3 zeigt die Druckeinstellung einer RSH-Pumpe.
Der max. zulässige Druck ist vom Druckbereich abhän-
gig.
DE
Standard Heizöl
und Bio Öl (FAME)
4,3 - 20 mm
/(cSt)
2
20 - 760 mm
2
/(cSt)
1400 - 3450 min
-1
15 - 35 bar (x 10
2
kPa)
1 - 5 bar (x 10
2
kPa)
21 bar (x 10
2
kPa)
-10 bis +70 °C
4 bar (x 10
kPa)
2
BI.DF.S3.52