Installation
Drop cable
An alternative to splicing 2 trunk lines in the connector on
the control card is to use a DeviceNet connection box or a
T-connector. For this installation, a drop cable is available
as an option. Drop cable order number: 195N3113. The
connector is a micro-style, male, with rotating coupling
3
3
nut, and fits into a Micro Device port.
Illustration 3.10 Drop Cable
10
®
VLT
DeviceNet MCA 104
Wiring Procedure for Enclosure Types A4-A5, B1-B4, and
C1-C4
Illustration 3.11 Wiring for Enclosure Types A4-A5, B1-B4, and
C1-C4
Danfoss A/S © Rev. 03/2015 All rights reserved.
1.
Push the cable through cable glands.
2.
Mount the fieldbus connector on the fieldbus
option (terminal V-, CAN_L, Drain, CAN_H, V+).
3.
Prepare the fieldbus cable by stripping a section
of the cable insulation. Keep the unshielded wire
as short as possible. For cable specifications, refer
to chapter 3.7.1 Cable Specifications.
4.
Connect the fieldbus cable wires to the terminals
according to the colour code of the wires, see
Illustration 3.8.
5.
Fix the cable screen to the metal base plate using
cable clamp or cable tie, see Illustration 3.11.
6.
Tighten cable glands securely.