Switch 3 on 2nd DIP switch set
Determines whether the audible alarm remains operational after levels
have dropped. In memory mode, the alarm remains and will need to be
manually reset. In non-memory mode, the alarm will automatically reset
after levels have dropped.
Example shows memory on
Switch 4 on 2nd DIP switch set
With switch 4 in the on position the BX444Mc is configured to indicate
oxygen levels. The function is determined by setting either excess oxygen
or oxygen depletion on the sensor itself (Duomo SGF104).
IMPORTANT NOTE.
If Oxygen setting is selected it is not possible to connect any other types of
sensors for any other gases. For example natural Gas or CO
BX444-Mc Operation
Before powering up the BX444-Mc once again check that all electrical connections are
correct.
1. Apply 230V supply to the Ph and N terminals. Ensure that the correct fuse is used in the supply. (3 or 5A max.)
2. All of the lights on the fascia will light up in turn. This will take approximately 20 seconds. This checks the function of all
the LED's.
3. The ON LED will remain flashing for about 2 minutes. This is the sensor warm-up period. The gas detector will not
provide gas detection during this period. When the ON light becomes constant the detector is in operation.
4. By pushing and maintaining pressure on the manual TEST button a function test can be performed for all pre-alarm
relays and main alarm relay, together with LED's and audible alarm.
The sequence will be:
a) The 8% LEL / 120
ppm
terminals 6 and 7 will be connected.
b) The 13% LEL / 200
ppm
terminals 8 and 9 will be connected and the audible alarm will continue to sound.
c) The 20% LEL / 300
ppm
10 and 11 will be connected, connection between terminals 10 and 12 will be broken and the audible alarm will continue
to sound. (When 'Intrinsic Safety' is on, terminals 10 and 11 will be broken and 10 and 12 will be connected). The relevant
Alarm LED's will light to show which zones are in alarm.
By releasing the the manual TEST button the lights will go out and the audible alarm will cease. If a latched alarm
function on the main relay is configured this will remain on until the RESET button is pressed.
5. In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas. The maximum
concentrations are;
- 40% LEL for methane in air
- 350
for carbon monoxide
ppm
- 0.85% (MOL) for propane
Any higher than this can reduce sensor life. NOTE: NEVER TEST USING NEAT GAS.THIS WILL POISON THE SENSOR.
6. To simulate a sensor fault situation disconnect the sensor plug. The detector will go into a FAULT alarm and the sensor
fault relay will be actuated. This will close the contacts between terminals 4 and 5 and open the contacts between
terminals 10 and 12 (Main Alarm relay). When the plug is reconnected the detector can be reset.
w: www.duomo.co.uk
-
and Pre-Alarm no. 1 LED will be actuated. The Pre-Alarm relay no.1 will be changed over and
and Pre-Alarm no. 2 LED will be actuated. The Pre-Alarm relay no. 2 will be changed over and
and Main Alarm LED will be actuated. The Main Alarm relay will be changed over and terminals
-
t: 01905 797989
-
f: 01905 774296
|
© Duomo (UK) Ltd. 2016