Belimo SHP Series Rekomendasi Instalasi - Halaman 3

Jelajahi secara online atau unduh pdf Rekomendasi Instalasi untuk Unit Kontrol Belimo SHP Series. Belimo SHP Series 5 halaman. Butterfly valves

Pre-Installation Procedure

1. Remove the protective face covers from the valve.
2. Inspect the valve to be certain the waterway is free from dirt and
foreign matter. Be certain the adjoining pipeline is free from any
foreign material such as rust and pipe scale or welding slag that
could damage the seat and disc sealing surfaces.
3. Actuators should be mounted on the valve prior to installation to
facilitate proper alignment of the disc in the valve seat.
4. The valve should be in the closed position. Make sure the open and
closed positions of the actuator correspond to the counter-clockwise
to open direction of rotation of the valve.
5. Cycle the valve to the fully open position, then back to the fully
closed position, checking the actuator travel stop settings for proper
disc alignment.
6. Check the valve identifi cation tag for valve class, materials, and
operating pressure to be sure they are correct for the application.
WARNING! Personal injury or property damage may result if the
valve is installed where service conditions could exceed the
valve ratings.
7. Check the fl ange bolts or studs for proper size, threading, and length.
REMEMBER: Install the valve with the disc in the full-closed position
using the appropriate fl ange gaskets on BOTH valve fl ange faces.

Valve Installation Procedure

The SHP High Performance Butterfl y Valve can be installed in the
pipeline with the shaft in the vertical, horizontal, or other intermediate
position. Based on applications experience, however, in media
with concentrations of solid or abrasive particles or media subject
to solidifi cation buildup, valve performance and service life will be
enhanced by mounting the valve with the shaft in the horizontal
position.
All SHP valves are bidirectional and can be mounted in the pipeline in
either fl ow direction; however, the preferred fl ow direction for all seat
styles and materials is with the seat retainer ring located upstream
(sus) to provide maximum seat protection.
For SHP Series valves
a. Noting the fl ow direction arrow on the tag, place the valve
between the fl anges, making sure the arrow on the tag points in
the direction of the fl ow.
b. Install the lower fl ange bolts loosely, leaving space for the fl ange
gaskets.
c. After inserting the fl ange gaskets, install the remaining bolts.
3. Using the sequence shown to the right, tighten the fl ange bolts
evenly to assure uniform gasket compression.
CAUTION: The SHP valve should be centered between the fl anges
and gaskets to prevent damage to the disc edge and shaft as a result
of the disc striking the fl ange, gasket, or pipe.
4. Electricity should be connected to the unit as specifi ed by the
actuator manufacturer.
5. The valve is now ready for operation.
800-543-9038 USA
NOTE
Actuator must be mounted
at or above pipe center line
for all actuator types.
Fig. 8
1
3
4
2
1
5
8
4
2
6
866-805-7089 CANADA
Installation Recommendations
SHP Series Butterfl y Valves
90°
90°
3
7
15
1
5
12
9
8
8
3
12
4
4
7
10
11
10
6
2
6
203-791-8396 LATIN AMERICA / CARIBBEAN
1
13
5
9
3
11
7
16
14
2
119