Belimo FS Series Lembar Instruksi - Halaman 2

Jelajahi secara online atau unduh pdf Lembar Instruksi untuk Mesin Belimo FS Series. Belimo FS Series 18 halaman. Replacement of multiproducts motors
Juga untuk Belimo FS Series: Petunjuk Manual (20 halaman), Penggantian (19 halaman)

Belimo FS Series Lembar Instruksi
®
UL
In the "Marking & Application Guide, Dampers for Fire Barrier and Smoke
Applications & Ceiling Dampers" April 2003 by Underwriters Laboratories
Inc.®, page 6 they state:
DAMPER ACTUATORS
"... field mounting or substitution of actuators is not covered within the scope
of the UL certification of the product. However, this does not necessarily
preclude replacement of actuators in the field. Like any appliance, field
servicing of these products is not covered under the scope of the UL
certification and factory follow-up service program. As with any part of the
damper, it is expected that replacement of actuators in the field be done in
accordance with the damper
This document follows the UL requirements and the acceptance testing
that is necessary to ensure proper operation of a fire and smoke damper after
actuator replacement.

Code and Standard Issues

In general, the administrative section of codes state that all mechanical and electrical systems
must be kept in working order and an individual section may state that all life safety devices and
systems must be operable. NFPA 80 (Fire) & NFPA 105 (Smoke) require periodic testing and
repair of dampers as soon as possible after any deficiency is uncovered.
Fire & smoke dampers are considered to be appliances and field replacement of components is to
be expected when failure of any component occurs.
The Authority Having Jurisdiction (local Fire Marshal and/or Building Official) must be consulted if
any blade or auxiliary switches are employed and are connected to the fire alarm system or to a
Fire Fighters Control System. A permit and inspection may be required since connections to an
alarm system have been touched.
INSTRUCTION SHEET
manufacture's
normal field servicing program."
Replacement of Multiproducts motors with Belimo FSxx Series
2