Modbus register description
Errors / Malfunctions
Note
Switching of the sensor type may
necessitate a restart of the actuator in order
to read out correct sensor values.
Actual sensor value
Register 9, 10, 11:
Series number
14 / 20
Belimo Gateway MP to Modbus RTU
(continued)
The status information is subdivided into actuator messages (malfunctions/maintenance) and
Register 6:
into errors detected by the Gateway. MPL actuators (Actuator Type: 6) don't generate
Malfunctions/Maintenance information.
Malfunctions
Maintenance
(Low Byte)
Faults
(High Byte)
The malfunction bits can be reset with Register 3 (command: 4) or with the Belimo PC-Tool.
Malfunctions 0 and 4 cannot be reset.
The error bits will be reset automatically by the Gateway.
Sensor type connected to the actuator; in the absence of sensor specification, the wiring at the
Register 7:
Sensor type
Y input of the MP actuator will have the effect of a local override.
Sensor type
0
None
1
Active sensor (mV)
2
Passive sensor 1k ()
Passive sensor 1...20k ()
3
4
Switching contact (0/1)
Note: The setting is not continuously backed up and should for that reason be updated
periodically.
Actual sensor value; dependent on the setting in Register 7
Register 8:
Each MP node has an unambiguous series number which is either impressed on or glued to the
node. The series number consists of 4 segments, although only parts 1, 2 and 4 are displayed
in the Gateway.
Example: 00839-31324-064-008
Register 9
T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes
Bit
Description
0
Excessive utilisation
1
Mechanical travel increased
2
Mechanical overload
3
-
4
Safety-relevant faults (fire & smoke only)
5
Damper test error (fire & smoke only)
6
Duct temperature too high (fire & smoke only)
7
Smoke detector tripped (fire & smoke only)
8
No response from MP node
9
Checksum error MP node
10
Error message MP node
11
Value outside of range
12
Function not available for actuator type
13
Time exceeded (fire & smoke only)
14
-
15
-
Register 10
1st part
2nd part
00839
Register 11
4th part
31234
008
www.belimo.com