CHASE FINISHING
If the chase is frame construction, the header over the chase opening must be a minimum of 66"
above the hearth floor. ½" masonry board should be installed over the entire area from the
header, between the studs, and up to the ½" offset ledge on the firebox. This board can be
screwed directly onto the fireplace face. The sheetrock can be butted up to the sides of the
fireplace. If installed on a wood floor, a hearth extension of 24" deep and extending 12" beyond
the hearth opening on both sides is required.
If the chase is masonry and the inside wall is extended above the fireplace, an adequate 1½ x
1½" L-iron mantle should be placed at the same height as the wooden header. Masonry board
covers the same opening.
THE FIREPLACE CANNOT BE USED AS ANY PART OF A
STRUCTUAL OR BEARING WALL
FIREBOX ASSEMBLY PROCEDURE
THE FIREPLACE SHOULD BE COMPLETELY ASSEMBLED
BEFORE BUILDING ANY CHASE OR FIREPLACE ENCLOSURE.
CONCRETE FLOOR INSTALLATION
If the fireplace is being installed flush with the floor, the supplied hearth split firebricks should be
laid out as illustrated in FIG 5, (pg. 5). They can be adhered to the floor with the refractory mortar
"Flue Glue" with a ¼"x ¼" tile applicator. After allowing to set, begin to assemble the firebox
starting with procedure #2, of the wood floor installation below.
WOOD FLOOR INSTALLATION
When the fireplace is being set over a wood floor, a heat barrier is required, see FIG 3 and FIG 4,
and step #1 below. Six sets of 2 split bricks 1¼" thick with a sheet of 24 gauge metal steel
sandwiched in between; which should be the same size of the base, and laid out as illustrated.
A hearth extension is required and must extend a minimum of 24" out from the face of the
fireplace and 12" beyond the fireplace opening on each side. The thickness of the extension shall
be a minimum of ½" masonry board and ¼" of ceramic tile or stone. The fireplace and hearth
extension can be raised to any height desired as long as the above specification are maintained
or increased.
The complete installation procedure following the installation of the heat barrier is shown and
described below.
1.
Base
1.
If the fireplace is being installed with the base(B), the hearth will be elevated 5" above the
finished floor. It can be elevated to any height desired by adding non-combustible bricks or
blocks under the base.
2.
Left Side
6