Introduction
The BASRT-B routes messages between BACnet/IP and
BACnet MS/TP networks as per the ANSI/ASHRAE 135-2004
standard. It allows BACnet/IP devices operating over Ethernet to
communicate with MS/TP devices. The router is configurable
via its internal webpage.
The BASRT-B comes in a metal case, is DIN-rail mounted and
is powered from a 24 VAC/VDC source. It has one isolated
MS/TP port and one 10/100 Mbps Ethernet Auto-MDIX port.
The MS/TP port offers a 3-pin terminal block with a removable
plug for the EIA-485 connection. Through this port, up to 254
devices can be addressed — as many as 31 full-load devices on
the attached segment. All MS/TP baud rates (as stated in the
BACnet standard) are supported.
The Ethernet port offers a shielded RJ-45 connector. Through
auto-negotiation and Auto-MDIX, it automatically matches its
duplex setting, data rate and communication pair usage to
whatever is needed by the attached equipment. Thus, only a
straight-through CAT5 cable is needed for hook-up.
The BASRT-B features a user-accessible switch to reset the IP
address, subnet mask and gateway address to the factory defaults.
Three LEDs are present: A power LED glows green when proper
power is provided. The Ethernet LED glows green for 100 Mbps
operation and yellow for 10 Mbps and flashes to indicate activity.
A green LED flashes when MS/TP traffic is received.
Each unit complies with Class A radiated and conducted emissions
as defined by EN55022 and CFR 47, Part 15, and is intended for
use in non-residential areas.
When using the BASRT-B to communicate on routed IP networks
(ones which use multiple IP subnets), a separate device with BBMD
functionality must be provided. If all IP devices use the same
subnet, then BBMD functionality is not required. For example, if
the BASRT-B uses IP address 192.168.1.1 and another BACnet/IP
device (which will communicate with the BASRT-B) uses 10.0.0.1,
then BBMD functionality is required from another device on your
network.