EMERGENCY STOP
If pressed, the red mushroom push button, placed in the middle of the door, stops the generator immediately and opens
the contact maker of the generator (CG) causing the block of the group..
To release the emergency status, set the programming switch in Lock position, turn the emergency push button and pull it
up.
FUEL PUMP CONTROL (on request)
The M02 module electronically controls the fuel level. It automatically controls the fuel pump so that the daily tank
requirements are constantly ensured. A push button enables the pump direct control with only a maximum safety level
safety function.
WAIT/PROG
A new conceived and remarkably useful LED has been fitted on the GCM02 module to assist the operator, namely the
WAIT/PROG LED. This LED flashes each time the timer is triggered informing the operator what is happening even over
long timing periods.
All LED are provided with a synoptic that makes the control panel easy to comprehend.
SUMMARY
The unit is normally programmed in AUTOMATIC mode.
When operating, the generator must be set in the LOCKED status.
If the generator is not to start even if the mains is disconnected it is to be set in the MANUAL MAINS status. The
reason for this is that if, while the generator is not working, there should be a failure in the electronics, the power
supply from the mains would be ensured in any case.
When , in case of mains lack, there is no need to use the generator, it must be always set in the MANUAL MAINS status.
Infact, in case of electronic breakdown- while the generator is not working- the power supply would always been ensured
by the mains.
HOW TO PROCEED IN CASE OF GENERATOR BREAKDOWN.
The alarm status is shown on the display. Whatever the anomaly, the cause is to be found first and then press the RESET
push button. The causes and the solutions differ depending on the type of anomaly involved:
1. Electrical anomalies due to min./max. voltage and frequency. If the anomaly should persist after having pressed the
RESET push button , call for a technical assistance;
2. Anomaly due to a low oil pressure, high motor temperature, low water or oil level, fuel reserve. Check the relative
levels (water, oil, fuel) and top-up if necessary then reset;
3. Anomaly of the dynamo battery charger. In this case request technical assistance;
4. Alarm due to local or remote emergency stop status. Set the programming switch on LOCKED mode, turn and pull the
active emergency push button, then reset;
5. Alarm due to failed starting. Try starting with manual control and advise the supplier;
6. The generator overload protection switch has tripped. It is to be reset manually by a qualified engineer (see simple
maintenance jobs section).