Aplisens WW-11ALW Panduan Pengguna - Halaman 11

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Monitor Aplisens WW-11ALW. Aplisens WW-11ALW 20 halaman.

Aplisens WW-11ALW Panduan Pengguna
8.

ELECTRICAL CONNECTION

8.1. Cable connection

All connecting and installation operations shall be performed with disconnected power
supply voltage and other external voltages, if used.
Failure to provide proper connection of the device may result in danger.
Risk of electric shock and/or ignition in potentially explosive atmospheres.

Figure 4. Connection diagram for WW-11ALW display without HART communication.

In the WW-11ALW display signal cables shall be led to the housing through cable ducts (cable
glands) and shall be connected to terminals (1), (2) and (3) of the terminal block according to the dia-
gram presented on the fig.4, 5 or 6 and the below table containing numbers of the terminals.
Maintain polarity of connection as in the following table.

Table 3. Table of markings of terminals in terminal block.

8.2. Cabling specification

Cables:
− unshielded cable is recommended when using only analogue signal;
− shielded cable is recommended for HART communication.
It is recommended to:
− connect display using twisted pair cable or shielded twisted pair cable;
− avoid leading conductors near power cables from the other cable systems;
− use earthing according to the recommendations.
Cross-section of wire of connecting conductor: ≤ 2,5 mm
Revision 01.B.003/2020.09
Polarization
Power supply
Transmitter
Terminal number
+
3
-
2
+
1
-
2
2
.
EN.IO.WW.11.ALW
11