Apollo 51000-600 Panduan Instalasi - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Alarm Asap Apollo 51000-600. Apollo 51000-600 15 halaman. Wireless combination smoke, heat and carbon monoxide detector
9.6 CO ALARM FUNCTIONAL TEST
After pressing and holding the CO test button for 12 seconds as in the previous
step, the detector will enter a CO GO/NO-GO test mode and the LED will blink
GREEN and BLUE for 2 minutes. While the detector is in the CO GO/NO-GO test
mode, using SDi SOLO C6 CO test gas, spray a small amount of CO test gas directly
into the gas entry port (See Section 2.1 Figure 1). The detector will sound
Temporal-4, the LED will blink RED along with the sounder and the CO alarm signal
will be sent to the control panel. Verify the signal was received at the control panel.
The CO test will automatically clear after testing, or after 2 minutes if no CO test gas
was used.
9.7 POST TESTING
If the detector fails to activate in any of the tests it should be cleaned, as outlined in
Section 10.1 of this manual, and the test should be repeated. If the detector still
fails to activate, return for servicing.
Once testing is complete, ensure the detector returns to normal operation mode
with the LED blinking GREEN every 12 seconds. If the detector is not in normal
operation, refer to Section 4.1 Table 1 - Detector Status LED & Sounder Operating
Modes to determine the detector state.
10. MAINTENANCE
TEST ONCE A WEEK
WARNING: USE ONLY BATTERIES SPECIFIED. USE OF DIFFERENT BATTERIES
MAY HAVE A DETRIMENTAL EFFECT ON THE DETECTOR.
YOUR DETECTOR SHOULD BE CLEANED AT LEAST ONCE A YEAR.
10.1 CLEANING
Remove the detector from the mounting base. Use a vacuum cleaner to vacuum
through the openings around the perimeter of the detector, or alternatively, use
compressed air to blow through the openings around the perimeter of the detector.
Wipe the detector clean with a damp cloth. Return the detector to the mounting
base.
11. FIRE DETECTION
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
• NFPA 72 states: Fire-warning equipment for residential occupancies are
capable of protecting about half of the occupants in potentially fatal fires.
Victims are often intimate with the fire, too old or too young, or physically or
mentally impaired such that they cannot escape even when warned early
enough that escape should be possible. For these people, other strategies such
as protection-in-place or assisted escape or rescue would be necessary.
• A battery powered alarm must have a battery of the specified type, in good
condition and installed properly.
• Smoke alarms must be tested regularly to make sure the batteries and the
alarm circuits are in good operating condition.
• Smoke alarms cannot provide an alarm if smoke does not reach the detector.
Therefore, smoke alarms may not sense fires starting in chimneys, walls, on
roofs, on the other side of a closed door or on a different floor.
• If the alarm is located outside the sleeping room or on a different floor, it may
not wake up a sound sleeper.
• Studies have shown that smoke and heat alarms may not awaken all sleeping
individuals, and that it is the responsibility of individuals in the household that
are capable of assisting others to provide assistance to those who may not be
awakened by the alarm sound or those who may be incapable of safely
evacuating the area unassisted.
• The use of alcohol or drugs may also impair one's ability to hear the smoke
alarm. For maximum protection, a smoke alarm should be installed in each
sleeping area on every level of a home.
• Although smoke alarms can help save lives by providing an early warning of a
fire, they are not a substitute for an insurance policy. Homeowners and renters
should have adequate insurance to protect their properties.
FAMILY ESCAPE PLAN
According to National Fire Protection Association (NFPA) there often is very little
time between the detection of a fire and the time it becomes deadly. This interval
can be as little as 1 or 2 minutes. Planning and practicing for fire conditions with a
focus on rapid exit from the residence are important. Drills should be held so that
all family members know the action to be taken.