Data Aire dap4 touch Manual Protokol - Halaman 10

Jelajahi secara online atau unduh pdf Manual Protokol untuk Sistem Kontrol Data Aire dap4 touch. Data Aire dap4 touch 13 halaman. Modbus tcp/ip protocol integration
Juga untuk Data Aire dap4 touch: Panduan Memulai Cepat (9 halaman), Panduan Pengguna (8 halaman), Petunjuk Instalasi (2 halaman)

Data Aire dap4 touch Manual Protokol
Point 
Index 
Compressor 3 Runtime - This applies when unit has four stages tandem
90
compressors - low
Compressor 4 Runtime - This applies when unit has four stages tandem
91
compressors. - high
Compressor 4 Runtime - This applies when unit has four stages tandem
92
compressors. - low
93
Condenser Runtime - high
94
Condenser Runtime - low
95
Constant Fan speed % of output in DX mode.
96
Constant Fan speed % of output in chilled water cooling.
97
Fan air flow setpoint (cfm) 1/10th scale*
98
Maximum damper (% of output) modulation in airside economizer*.
99
Zone Airflow Setpoint (1/100th of actual)*
100
Zone Airflow Setpoint from the server (LSB) 000-999*
101
Zone Airflow Setpoint from the server (1/100th actual cfm)*
102
1/10th of the total zone airflow*
103
Economizer Runtime - high*
104
Economizer Runtime - low*
105
Relative humidity of the outside air in %*
106
Oustide air enthalpy in KJ or BTU*
107
Return air enthalpy in KJ or BTU*
108
Analog value of damper in %*
109
Fan speed modulation percentage (bases on output singal)
110
Setting of HP alarms/hr before comp is locked out, 1=disabled*
111
Number of HP alarms C1 had within an hour*
112
Number of HP alarms C2 had within an hour*
113
Number of units selected by ZM for standby based on current schedule*
114
Number of units currently running in the zone*
115
State of unit (at address 1). 1,12&13 = On, 2 thru 9 = Off*
116
State of U2 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
117
State of U3 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
118
State of U4 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
119
State of U5 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
120
State of U6 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
121
State of U7 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
122
State of U8 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
123
State of U9 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
124
State of U10 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
125
State of U11 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
126
State of U12 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
127
State of U13 when zone master is enabled. (1,12&13 is running, 2-9 is Off)*
 
 
Data Aire's dap4 Modbus TCP/IP
Description 
Document: 600‐000‐961 version 4.0 
Read/
Variable Name 
Write 
R
C3_Hours_L
R
C4_Hours_L
R
C4_Hours_H
R
Cond_Hours_H
R
Cond_Hours_L
R
DX_Fan_Speed
R
CW_Fan_Speed
R
Fan_AF_sp
R/W
Damper_max
R/W
ZM_Airflow_SP
R/W
Unity_Airflow_SP_lsb
R/W
Unity_Airflow_SP
R
ZM_Airflow
R
Econ_Hours_H
R
Econ_Hours_L
R
Outside_Hum_dsp
R
Outside_Enthalpy
R
Return_Enthalpy
R
Damper_Mod_disp
R
Fan_Out
R/W
HP_Lockout_Cnt
R
C1_HP_Count
R
C2_HP_Count
R
Num_Stdby
R
Num_Units_On
R
Unit Status
R
Unit2_status
R
Unit3_status
R
Unit4_status
R
Unit5_status
R
Unit6_status
R
Unit7_status
R
Unit8_status
R
Unit9_status
R
Unit10_status
R
Unit11_status
R
Unit12_status
R
Unit13_status
Data 
Modbus 
Type 
TCP/IP 
I
35091
I
35092
I
35093
I
35094
I
35095
I
35096
I
35097
I
35098
I
45099
I
45100
I
45101
I
45102
I
35103
I
35104
I
35105
I
35106
I
35107
I
35108
I
35109
I
35110
I
45111
I
35112
I
35113
I
35114
I
35115
I
35116
I
35117
I
35118
I
35119
I
35120
I
35121
I
35122
I
35123
I
35124
I
35125
I
35126
I
35127
I
35128
10