Data Aire dap4 touch Manual Protokol - Halaman 9
Jelajahi secara online atau unduh pdf Manual Protokol untuk Unit Kontrol Data Aire dap4 touch. Data Aire dap4 touch 13 halaman. Modbus tcp/ip protocol integration
Juga untuk Data Aire dap4 touch: Panduan Memulai Cepat (9 halaman), Panduan Pengguna (8 halaman), Petunjuk Instalasi (2 halaman)
Point
Index
55
Dehumidifier Runtime - High
56
Dehumidifier Runtime - Low
57
Fan pressure setpoint inches of water
58
Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None
59
Value sent to optional analog output#1*
60
Value sent to optional analog output#2*
61
1/10th Current Fan Airflow - Based on calculated Pressure Diff formula*
62
Name of the sensor 1*
Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
63
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}*
64
Name of the sensor 2*
Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
65
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}*
66
Name of the sensor #3*
Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
67
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}*
68
Name of the sensor 4*
Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
69
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}*
70
CW Fan speed (%) controlled by BMS
71
DX Fan speed (%) controlled by BMS
72
Maximum Fan speed (% of output) modulation.
73
Minimum Fan speed (% of output) modulation.
74
Fan pressure setpoint (0.001 inches of water)*
75
Fan pressure band (0.001 inches of water)*
76
Maximum air flow that the unit can deliver*
77
Minimum air flow limit of setpoint from BMS or valve modulation.*
78
Fan K Factor*
79
Number of fans installed in this unit*
80
Minimum Damper (% of output) modulation for airside economizer*.
81
Heater 2 Runtime - high
82
Heater 2 Runtime - low
83
Heater 3 Runtime - high
84
Heater 3 Runtime - low
Energy Saver Runtime - This optional point applies to energy saver units
85
only -high*
Energy Saver Runtime - This optional point applies to energy saver units
86
only - low*
87
Chilled Water Runtime - This applies to chilled water units only - high
88
Chilled Water Runtime - This applies to chilled water units only - low
Compressor 3 Runtime - This applies when unit has four stages tandem
89
compressors - high
Data Aire's dap4 Modbus TCP/IP
Description
Document: 600‐000‐961 version 4.0
Read/
Variable Name
Write
R
Dehum_Hours_H
R
Dehum_Hours_L
R/W
Fan_Pr_sp_hi
R
AutoFlush_dly
R
Y4_Out
R
Y5_Out
R
Air_Flow
R
Opt_Snsr1_name
R
Ain_type
R
Opt_Snsr2_name
R
Ain_type
R
Opt_Snsr3_name
R
Ain_type
R
Opt_Snsr4_name
R
Ain_type
R/W
CW_Fan_Speed_bms
R/W
DX_Fan_Speed_bms
R/W
Fan_Speed_max
R/W
Fan_Speed_min
R/W
Fan_Pr_sp
R/W
Fan_pr_band
R/W
Fan_AF_max
R/W
Fan_AF_min
R/W
Fan_Kfactor
R/W
Num_Fans
R/W
Damper_min
R
Ht2_Hours_H
R
Ht2_Hours_L
R
Ht3_Hours_H
R
Ht3_Hours_L
R
Engy_Hours_H
R
Engy_Hours_L
R
CW_Hours_H
R
CW_Hours_L
R
C3_Hours_H
Data
Modbus
Type
TCP/IP
I
35056
I
35057
I
45058
I
35059
I
35060
I
35061
I
35062
I
35063
I
35064
I
35065
I
35066
I
35067
I
35068
I
35069
I
35070
I
45071
I
45072
I
45073
I
45074
I
45075
I
45076
I
45077
I
45078
I
45079
I
45080
I
45081
I
35082
I
35083
I
35084
I
35085
I
35086
I
35087
I
35088
I
35089
I
35090