Data Aire DAP III Petunjuk Manual - Halaman 11

Jelajahi secara online atau unduh pdf Petunjuk Manual untuk Sistem Keamanan Data Aire DAP III. Data Aire DAP III 13 halaman. Bacnet integration

Data Aire, Inc. DAP

4.3.2 Object List

Object Name
Cooling Stages On
Heating Stages On
Chilled Water Valve Open
Percentage
Humidifier Valve
(Optional)
High Temperature In The Last
24Hrs.
Low Temperature In The last 24Hrs.
High Humidity In The last 24Hrs.
Low Humidity In The Last 24Hrs.
Cooling Utilization
Heating Utilization
Chilled Water Utilization
Humidifier Utilization
Compressor 1 Runtime
Compressor 2 Runtime
Compressor 3 Runtime
Compressor 4 Runtime
Heat Stage 1 Runtime
Heat Stage 2 Runtime
Heat Stage 3 Runtime
Humidifier Runtime
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Instance
Object Description
No. AV
1
Cooling stages are currently on (0-5).
This point only applies to DX unit
2
Heating stages are currently on (0-4)
3
Chilled Water valve open percentage
(0-100%). This point only applies to
chilled water unit.
4
Humidifier valve open percentage (0-
100). This point only applies to unit
that has an optional modulating
humidifier
5
Maximum value of the Return Air
temperature in the last 24 hours
6
Minimum value of the Return Air
temperature in the last 24 hours
7
Maximum value of the Relative
humidity in the last 24 hours
8
Minimum value of the Relative
humidity in the last 24 hours
9
Cooling Utilization of the last hour
(0-100 percent). This applies to DX
unit only
10
Heating utilization of the last hour
(0-100 percent)
11
Chilled Water valve utilization of the
last hour (0-100 percent). This
applies to unit with Chilled water
unit only
12
Humidifier utilization of the last hour
(0-100 percent)
13
The total runtime of the compressor
#1 (Hour)
14
The total runtime of the compressor
#2 (Hour)
15
The total runtime of the compressor
#3 (Hour)
16
The total runtime of the compressor
#4 (Hour)
17
The total runtime of the heating stage
#1 (Hour)
18
The total runtime of the heating stage
#2 (Hour)
19
The total runtime of the heating stage
#3 (Hour)
20
The total runtime of the humidifier
(Hour)
Page 11 of 13
Present-
Value
Writeable
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No