4 BACnet Object Definitions
4.1 Binary Value Objects
4.1.1 Readable fields
Object-identifier
Object-name
Object-type
Present-value
4.1.2 Object List
Object Name
Dehumidification
Humidification
Energy Saver
Cooling Held
Heating Held
Humidification Held
Dehumidification Held
Reheat During Dehumidification
Water Under Floor
No Air Flow
Dirty Filter
Humidifier Problem
Low Voltage Warning
Fire-Stat Trip
Compressor Short Cycle Warning
Power Problem
Humidity Sensor Problem
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Status-flags
Event-state
Out-of-service
Instance
Object Description
No. BV
1
Unit is dehumidifying
2
Unit is humidifying
3
Energy Saver function is active
4
Cooling is inhibited
5
Heating is inhibited
6
Humidification is inhibited
7
Dehumidification is inhibited
8
Reheat on during dehumidification
9
Water Under Floor detection alarm
10
Loss of the air flow alarm
11
Filter clogged alarm
12
Loss of the humidifier make-up water
pressure alarm
13
DC power of the DAP III boards drops
below the required level
14
The return air temperature rises above
the Firestat temperature setting limit
15
Compressor short cycle warning is active
16
Power reset or unit restart notification
17
Faulty Humidity sensor detected