Appion G1 Single Panduan Pengoperasian - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Pengoperasian untuk Peralatan Uji Appion G1 Single. Appion G1 Single 20 halaman. Single cylinder

Appion G1 Single Panduan Pengoperasian
Machine Usage
⚠ CAUTION
To reduce the risk of injury or product damage, read this entire operating manual, with
particular emphasis on the Safety and Preparation sections (Page 4-7), prior to operating the G1Single.

STANDARD RECOVERY PROCEDURE

1. Setup the G1Single as shown in Diagram 2 (below). Make sure that all connections are tight.
A. Connect the AC/R System Liquid Port to the Manifold high side.
B. Connect the AC/R System Vapor Port to the Manifold low side.
C. Connect the Manifold Center port to the G1Single input port.
D. Connect the G1Single output port to the Liquid Port on the Recovery Cylinder.
Diagram 2
Recover into the Liquid Port of the
Recovery Cylinder for faster recovery.
OPTIONAL: To reduce the effect of
high back pressure at the end of the
recovery process, recover into the
Vapor Port instead (may increase
recovery times).
2. Connect the G1Single to a grounded power source for the proper voltage of the machine (115v/230v).
If using an extension cord, follow the cord sizing guidelines on Page 4.
3. Close both valves on the Manifold Gauge Set.
4. Open the Recovery Cylinder Liquid Port.
5. Turn on the G1Single. The compressor and fan should start.
6. Slowly open the Manifold High Side (liquid) valve. Removing the liquid first will keep the recovery
time to a minimum.
7. When all the liquid has been removed, slowly open the Manifold Low Side (vapor) valve. Both sides
should now be fully open to maximize vapor flow.
8. Continue to run the G1Single until the EPA-required vacuum is achieved.
9. Close both valves on the Manifold Gauge set.
10. Turn off the G1Single.
11. Close the valves on the Recovery Cylinder and disconnect the hoses.
G1SINGLE OPERATION MANUAL
© 2012 APPION INC. - ALL RIGHTS RESERVED
8