Datakom DKG-117 Panduan Pengguna - Halaman 11

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Relai Datakom DKG-117. Datakom DKG-117 12 halaman. Synchroscope and check synch relay
Juga untuk Datakom DKG-117: Panduan Pengguna (12 halaman)

Datakom DKG-117 Panduan Pengguna
DKG-117 User Manual
V-01
(24.03.2014)

9. TECHNICAL SPECIFICATIONS

Generator voltage: 300 V-AC max. (Ph-N)
Generator frequency: 0-100 Hz.
Busbar voltage: 300 V-AC max. (Ph-N)
Busbar frequency: 50/60 Hz.
Digital inputs: 0 - 30 V-DC. Internally connected to battery positive via 4700 ohm resistor.
DC Supply Range: 9.0 to 33.0 V-DC
Cranking dropouts: survives 0 V for 100ms.
Typical Standby Current: 100 mA-DC
Maximum Operating Current: 150 mA-DC (Relay outputs open)
Check Synch Relay Output: 10 A / 28V-DC
Operating temp.: -20C (-4F) to 70 C (158F).
Storage temp.: -30C (-22F) to 80 C (176F).
Maximum humidity: 95% non-condensing.
IP Protection: IP65 from front panel, IP30 from the rear.
Measurement category: CAT II
Air category: Pollution degree II
Dimensions: 102x102x53 mm (WxHxD)
Panel Cut-out Dimensions: 92x92 mm minimum.
Mounting: Front panel mounted with rear retaining steel spring.
Weight: 170 g (approx.)
Case Material: High Temperature ABS (UL94-V0, 100C)
- 11 -