Datakom DKG-175 Panduan Pengguna

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Beralih Datakom DKG-175. Datakom DKG-175 11 halaman. Automatic transfer switch

Datakom DKG-175 Panduan Pengguna
DKG-175 User Manual
DESCRIPTION
Datakom DKG-175 is a DIN Rail mounted ATS
controller not requiring DC supply. Thanks to this
feature, it is not required to carry the DC supply from
the battery to the transfer panels, providing ease of
installation.
The unit monitors 3-phase mains voltages, sends
remote start command to the generating set and
performs changeover of both generator and mains
contactors.
The front panel leds provide information about mains
and generator power availability as well as contactor
positions. Moreover, mains phase voltages and
frequency can be seen on front panel.
Mains voltage and frequency high and low limits,
mains waiting timer, mains fail timer, generator start
delay, cooldown timer and mains contactor timer are
front panel programmable. Generator contactor timer
is adjustable between 1 and 40 seconds through front
panel knob.
DKG-175 AUTOMATIC
TRANSFER SWITCH
(WITHOUT DC SUPPLY)
DIN Rail mounted
No DC supply required
Mains phase order check
Adjustable MCB and GCB delays
Programmable mains frequency and voltage high
and low limits
Programmable delay timers
10A/250VAC MCB and GCB outputs
10A/28VDC remote start output
Isolated mains and genset inputs
Test mode
V-1
(24.07.2017)
FEATURES