Elsner WS1 Style-4 PF Instruksi Singkat

Jelajahi secara online atau unduh pdf Instruksi Singkat untuk Sistem Kontrol Elsner WS1 Style-4 PF. Elsner WS1 Style-4 PF 2 halaman.

EN
Brief Instruction
Mounting of WS1 Style
Item numbers 60180-60189 (WS1 Style), 60194 (WS1 Style-4 PF)
The manual with additional information about commissioning,
functions and use of the controls WS1 Style can be download-
ed from www.elsner-elektronik.de in the menu area "Service/
Downloads".
Warning, mains voltage! National legal regulations are to be
observed. Installation, inspection, commissioning and
troubleshooting of the device must only be carried out by a
competent electrician.
Notes on wireless equipment
When planning facilities with devices that communicate via radio, adequate radio
reception must be guaranteed. The range will be limited by legal regulation and
structural circumstances. Avoid sources of interference and obstacles between re-
ceiver and transmitter, that could disturb the wireless communication. Those
would be for example:
Walls and ceilings (especially concrete and solar protection glazing).
Metal surfaces next to the wireless participants (e. g. aluminium
construction of a conservatory).
Other wireless devices and powerful local transmitters (e.g. wireless
headphones), which transmit on the same frequency. Please maintain a
minimum distance of 30 cm between wireless transmitters for that reason.
Preparing the installation location
The device must only be installed and used in dry, interior
spaces. Avoid condensation.
The device is to be installed flush to the wall surface. When selecting an installation
location, please ensure that the measurement results of the integrated temperatu-
re/humidity sensor are affected as little as possible by external influences. Possible
sources of interference include:
Direct sunlight
Drafts from windows and doors
Draft from ducts which lead from other rooms to the concealed box
Warming or cooling of the building structure on which the device is
mounted, e.g. due to sunlight, heating or cold water pipes
Connection lines which lead from warmer or colder areas to the device
Cut-out dimensions for concealed box:
W = 166 mm +1 -0 | H = 116 mm +1 -0 | D = 80 mm
An external antenna can be connected in order to improve wireless communicati-
ons. During installation, a conduit 50 cm in length should be placed beneath the
recessed housing, in which the external antenna can be mounted (antenna dimen-
sions approx. 565 x 8 x 5, L × W × H in mm):
Conduit angled diagonally dow-
Conduit angled vertically downwards (only
nwards (for cable access from
for cable access from above!)
above or below)
concealed
concealed
box
box
cable
45°
M16 conduit, 50 cm in length
Preparing for installation
The display unit is held by magnets. Re-
move the front part from the concealed
box.
Caution: The display is connected
with a flat-ribbon cable to the circuit
board in the concealed box.
Wall-fitting
Cavity wall fitting
Assembling the control unit with concealed box
During electrical installation, please introduce all connection cables into the con-
cealed box through the lower or upper side wall. In the process, keep the individual
connection wires short to prevent long reserve loops.
After connecting the cables screw the security covering onto the concealed box.
cable
The security covering must be fixed before the control is put
into operation! It prevents contact with current-carrying parts
in the concealed box.
M16 conduit,
50 cm in length
By adjusting the mounting screws, the display unit will rest flat on the wall later
and be held by the magnets safely.
Connect the flat ribbon cable to the display and place the display unit on the con-
cealed box. The magnets must be attracted by the mounting screws considerably
and the display unit must rest tightly on the concealed box.
Mounting of WS1 Style • Version: 30.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Mounting of WS1 Style
Loosen the plug so that the display unit
can be removed.
Remove all parts of the transportation
lock/packing.
The security covering in the concealed
box is attached with four screws: Loosen
the screws and take off the security cover-
ing.
Remove the circuit board from the con-
cealed box to be installed a keep it in a
place where it is protected from dirt. It
may never be exposed to dust or mo-
isture!
Place the concealed box in the wall so
that the arrows point upwards.
For fitting, screw the cover (board) on to
the concealed box with the enclosed
screws.
Clamp the concealed box to the wall with
the four enclosed screws.
Upon delivery, the pouch containing the
or
assembly screws can be found in the con-
trol unit's concealed box.
Adjust the screws of the magnetic moun-
1
ting with the enclosed template. Each of
the four screws must be adjusted individi-
ally in height.
2
When the edge of the template rests on
the wall surface (1), the template must
rest on the mounting screws as well (2).
1
Structure of the connector board WS1 Style
1
4
3
5
17
7
8
16
1 Mains connection
12 Wall button 4
L/N/PE 230 V/50 Hz
(10:+12V|11:Up|12:Down)
2 Drive group 1
13 Weather station (terminals 1-2)
3 Drive group 2
Wire assignment: red = 1, black = 2,
4 Drive group 3
yellow and white = not connected
5 Drive group 4
14*Multifunctional input 1
6 Outer conductor L1
(terminal 3: +12 V | 4: GND | 5: IN)
7 Multifunctional output 1
15*MF input 2 (6: +12 V | 7: GND | 8: IN)
(potential-free)
16 Connector for flat-ribbon cable to
8 MF output 2 (potential-free)
front board
9 Wall button 1
17 Microfuse T6,3 A
(terminal 1: +12 V | 2: Up | 3: Down)
10 Wall button 2
* Supply voltage e. g. indoor sensor
(4: +12 V | 5: Up | 6: Down)
possible via MF inputs
11 Wall button 3
(No. 14, terminal 3(+), 4(-) and
(7: +12 V | 8: Up | 9: Down)
No. 15, terminal 6(+), 7(-)),
max. 50 mA altogether.
Structure of the connector board WS1 Style-PF
3
1
5
4
8
6
7
16
1 Mains connection
12 Wall button 4
L/N/PE 230 V/50 Hz
(10:+12V|11:Up|12:Down)
2 Drive group 1
13 Weather station (terminals 1-2)
3 Drive group 2
Wire assignment: red = 1, black = 2,
4 Drive group 3
yellow and white = not connected
5 Drive group 4
14*Multifunctional input 1
6 Multifunctional output 1
(terminal 3: +12 V | 4: GND | 5: IN)
(potential-free)
15*MF input 2 (6: +12 V | 7: GND | 8: IN)
7 MF output 2 (potential-free)
16 Connector for flat-ribbon cable to
8 Microfuse T630 mA
front board
9 Wall button 1
(terminal 1: +12 V | 2: Up | 3: Down)
* Supply voltage e. g. indoor sensor
10 Wall button 2
possible via MF inputs
(4: +12 V | 5: Up | 6: Down)
(No. 14, terminal 3(+), 4(-) and
11 Wall button 3
No. 15, terminal 6(+), 7(-)),
(7: +12 V | 8: Up | 9: Down)
max. 50 mA altogether.
1
2
6
15
12
11
14
13
10
9
2
12
15
14
11
13
10
9