The break tank is constructed to have a weir slot as required by the water bylaws to prevent back flow contamination, if
the inlet ball valve or NRV suffered a catastrophic failure the overflow may not be able to keep up with the inflow in
which case excess water will be ejected through the weir slot and onto the plant room floor, if this is not acceptable then
consideration should be given to fitting the wash down set onto a tray with overflow to a drain.
Volt Free Contacts – Pump Running
Both open and closed volt free contacts are available which indicate if the pump is running. See appropriate
drawing for volt free contact wiring configurations. Rating 1A 50v maximum.
Commissioning
1.
Ensure the water tank is clean.
2.
With the power supply off. Open the water supply to the water tank and fill with water until the
ball valve closes and stops further filling. Check the water level is correct and all joints are
sound.
3.
Check the pump has been fully evacuated of all air by removing the bleed screw of the pump
and allow water to escape until no air is present, replace the bleed screw.
4.
Open discharge valve and power the product, the pump should then start to run and push all
air out of the discharge system, when free of air close the discharge valve and the flow will
stop and the pump will switch off after approximately 10 seconds.
Operation
When a draw off point connected to the system is opened the pressure will start to fall and the pump will start
Supply
to pressurise the system. The pump will continue to run until demand ceases completely and flow has stopped
230v single phase + Earth
(< 3l/m) the pump will run for approximately 10 seconds and will then shutdown.
Connect to a suitable thermal switch or fused supply
The pressure will now be sitting at the pump closed valve head value.
A high sensitivity differential switch is also recommended (0.03A)
Lack of water
If the pump controller senses a lack of water the pump will be stopped automatically after approximately 10
seconds and the red failure light will be illuminated.
If the water supply comes back online and a discharge is open the pump controller will automatically reset and
start the pump.
If the water supply has been reinstated and the pump has not started automatically the reset button can be
L
operated which will cause the pump to run for approximately 10 seconds and prime the system, if successful the
N
pump will then operate normally.
E
Maintenance
Routine check (6 monthly intervals)
1.
Check the pump produces the correct pressure.
2.
Check that the pump operates without undue noise or vibration.
3.
Check the break tank is clean and that the correct water level has been maintained.
4.
Check that all screws are tight on electrical components.
5.
Check that the earth connections are tight and making good contact.
Mains water supply 15mm
Pump removal
Isolate power supply feeding pump set.
Isolate water inlet feeding pump set.
Open an outlet to release system pressure
Isolate the valve located on each flexible connector and remove the flexible from the pump suction and
discharge ports, the pump can now be un-bolted from the base and pulled forward.
The electrical cable can now be removed from the pump terminal box.
The new pump can now be fitted reversing the above procedure.
[email protected] | 01452 300110
01452 300110
|
Electrical connections
Pump controller
L
U
N
V
E
E
M
Terminals 1 & 2 close for pump run
Terminals 1 & 3 open for pump run
Pump motor
1 metre of
3 core 1mm2 cable
Gland for wiring
to volt free contact
Volt free contact
box
Relay
Wall mounting
fixing holes
4 x M8 fixing bolts
System
connection
3
15mm push fit
NOTE
.
Installation of this product should not be carried
out until the installation and operating instruction
have been read and fully understood.
Installation Notes.
1. This product sho
2. It is recommend
3. Isolating valves
4. The system pipe
5. Electrical conne
local site regulat
6. Cold water supp
a low pressure s
7. The 22mm over
4