Cookson FDO-A10E Panduan Pemilik - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Pemilik untuk Sistem pembukaan pintu Cookson FDO-A10E. Cookson FDO-A10E 19 halaman. Industrial duty fire door operator
UPGRADED UNIT W/ADDENDUM
JUMPER CONFIGURATIONS
TERMINALS
+ TO 19 = CHANGES ALARM CLOSURE
DELAY FROM 10 SECONDS TO
IMMEDIATE.
+ TO 20 = CHANGES SOUNDER STROBE
FROM ACTIVATION ON ALARM ONLY TO
ANY TIME THE MOTOR IS MOVING THE
DOOR.
+ TO 21 = WILL CAUSE DOOR TO RETURN
TO THE FULLY OPEN POSITION ON ALARM
RESET.
WARNING
DO NOT SELECT THIS OPTION UNTIL ALL OTHER
FUNCTIONS OF DOOR HAVE BEEN VERIFIED AND
LIMITS HAVE BEEN SET. PERSONAL INJURY OR
EQUIPMENT DAMAGE COULD RESULT.
CAUTION: DISCONNECT POWER BEFORE
OPENING COVER AND INSTALLATION.
NOTES:
1. REFER TO BASIC WIRING DIAGRAM
(PG9) FOR ADDITIONAL INFORMATION.
9001(7) ECN 1057 4/10/010
FDO-A10 WIRING DIAGRAM
13
12
11
10 -
+ TO 22 = WILL DISABLE ANY OPEN FUNCTION
DURING AN ACTIVE ALARM CONDITION. DOOR
WILL STOP AND NOT RELEASE UPON CONTACT
WITH AN OBSTRUCTION, AND OPEN BUTTON
WILL NOT OPERATE. THIS SETTING ONLY
AFFECTS OPERATION DURING AN ACTIVE
ALARM CONDITION.
M
5
4
3
2
1
11