Cookson Firefly IV MV Panduan Pemilik - Halaman 3
Jelajahi secara online atau unduh pdf Panduan Pemilik untuk Sistem pembukaan pintu Cookson Firefly IV MV. Cookson Firefly IV MV 13 halaman. Release device
SPECIFICATION
Input Power*:
Alarm Dry Contact Rating:
Lower Limit Microswitch Rating:
Door Close Warning Power:
Status Dry Contact:
Frequency:
Release Pull:
Fuses:
*Input voltage [standby/full load**/start current]: 115VAC [0.5/0.6/1.1A], 230VAC [0.25/0.3/0.55A],
24VAC [0.5/0.8/1.8A] or 24VDC [0.2/0.4/1.8A].
**Full load current only required for optional warning device(s).
Must install with UL approved fusible links.
24V input power can be 24VDC or 24VAC or 24VDC from an approved UL1481 regulated power
supply.
18-gauge wire recommended.
For "Indoor Dry" location use only.
Close warning power is provided for less than a minute. Any fire Listed audible or visual device
may be used if the 24VDC input is powered by a UL1481 regulated power supply. When input
power is 115VAC, 230VAC or 24VAC, please connect the following compatible devices:
Bridgeport Fitting Inc Series 840P & 840T and Federal Signal Corp Model LP6 and Series LP3.
Note: Door Close Warning Output is only functional when the box has input power.
INSTALLATION
WARNING
-
For "Indoor Dry" location use only. All wiring must satisfy the most current version of
NFPA72 – National Fire Alarm Code and the National Electric Code.
-
18-gauge wire is recommended
115VAC, 0.5A; 230VAC, 0.25A ; 24VAC, 0.5A; 24VDC, 0.2A
24VDC, 0.08A, 5.16 ohms max line impedance
30VDC, 0.08A, 5.16 ohms max line impedance
24VDC @Max. 0.23A, Resistive, Special Application (see
below)
Rating: 30VDC/VAC, 2A, Resistive Load
50Hz or 60Hz
50 lbs (22.7kgs)
F1: 4A@250V, Fast-Act Type
F2: 3A@250V, Slo-Blo Type
Disconnect power supply before servicing.
2