11. Wiring diagrams

Connection ATICS-2-DIO
Terminal
1,3
5,7
4,6
l, k
GND, En/Ex
IN1/GND, IN1
NC, NC
24, 34, 44, 21
IN2, IN3, IN4, IN2-4 GND
A, B
14, 12, 11
Warning: Risk of destruction if connection incorrect
The terminals labelled GND must not be connected to PE.
ATICS-DIO_D00080_02_Q_XXEN/04.2017
Meaning
Connection line 1 (input line) L,N
Connection line 2 (input line) L,N
Connection line 3 (output line) N,L
Connection measuring current transformer STW3 (T3) for monitoring the load current downstream
the transfer switching device (short-circuit monitoring)
Connection must not be used. These terminals are solely intended for future extensions!
Digital input, configurable, for example, for monitoring the switch position of the transfer switching
device
not used
3 alarm relays (1 N/O contact each), 21 = common connection for the three alarm relays
3 digital inputs
BMS bus connection
Alarm relay, programmable function
ATICS-...-DIO Quick start