GAC EEG6550 Series Manual - Halaman 7
Jelajahi secara online atau unduh pdf Manual untuk Beralih GAC EEG6550 Series. GAC EEG6550 Series 13 halaman. Enhanced electronic governor
6
FEATURES (CONTINUED)
ServIce HoUr meTer
SRVT sets the hour meter for an alert at the selected service interval. Range of adjustment is 1 to 2000 hours, the default value is 500
hours. If the service time is expired, the displayed number will be '0' or negative.
Disable SRVT by selecting OFF on the Advanced Menu parameter page. Default is Disabled - OFF.
7
ADVANCED PARAMETERS MENU
Display Special
menu Parameters:
Selecting Parameters:
adjust Parameters:
return to Quikset menu:
aDvanceD menU ParameTerS (confIGUraBle)
PARAME-
DEFINITION
TER
Auxiliary Input Enable
AUx
145 Hz/V, 5 V nominal Range: 1-9 V
Auxiliary Input Polarity
V DC: Speed Increases w/ Increased
AUxP
Voltage or dEC: Speed Decreases w/
Increased Voltage
Variable Speed or Trim Select
VSPD
(On=Variable Speed, Off=Trim)
Variable Speed Input Signal
VSMD
Resistive / Current / Voltage
VGLO
Variable speed GAIN, low speed setting
Variable speed GAIN, high speed
VGHI
setting
LFG
Light Force Governor
Lead Circuit - For Increased Governor
LEAD
Response / Increased GAIN Adjustment
Speed Anticipation
SANT
Improved Transient Performance
NLCU
No Load Current - Amps
FLCU
Full Load Current - Amps
SSWS
Speed Switch Setting - RPM
Speed Switch: Normally Closed (nC) or
SSWP
Normally Open (nO)
Speed Switch Latch On - Resets after
SSWL
Cycling Power, Latch Off Automatically
Resets at '0' RPM
JADR
CAN J1939 Address
SRVT
Service Reset - Hours
Hold ALL 3
AUx appears in display
Previous
Next
Parameter
Parameter
Increase
Parameter
Decrease
Parameter
Hold ALL 3
RANGE
Off, On
dEC, InC
Off, On
rES/
Cur/5dc
1 - 100
1 - 100
Off, On
Off, On
Off, On
0.0 - 9.5
0.5 - 10.0
100 to
4000
nC / nO
On / Off
0 - 253
1 - 2000
1.
After 3 minutes of no user input, EEG switches to
until
Quikset Menu.
2.
Lock is displayed when attempt to change a
Read-Only parameter.
for 2 seconds
aDvanceD menU ParameTerS (reaD onlY)
DE-
PARAME-
FAULT
TER
SREV
Off
BID
AREV
dEC
FLTH
Off
DATL
5dc
FLTL
50
50
Off
ON
Off
0.5
4.0
2000
nO
ON
JADR parameter identifies J1939 addresses, 0 to 253. Default set to
0
'0'. See Section 13, J1939 CAN Information, for a description of the
Off
transmittable data.
EEG6550 Enhanced Electronic Governor 5-2020-A1
7
Governors America Corp. © 2020 Copyright All Rights Reserved
DEFINITION
Software revision number
Software build identifier
Assembly revision: Identifies board hardware configu-
ration, not software.
Highest fault code since power up. Aids in trouble
shooting.
Supplemental data associated with last fault code.
Aides in troubleshooting.
Last fault code detected. Associated data is DATL and
aids in trouble shooting.
PIB1118