Great Lakes VRX Panduan Petunjuk Instalasi - Halaman 8
Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Rak dan Dudukan Great Lakes VRX. Great Lakes VRX 12 halaman. Highlander variable depth racks
![Great Lakes VRX Panduan Petunjuk Instalasi](/uploads/products/server2/1870756/1870756.jpg)
3. Assemble bottom width brackets to vertical uprights.
3/8" Ext. Tooth Washer
3/8-16 x 1" lg Hex
Head Bolt
4. Use appropriate tool and tighten all hardware (54 ft-lb torque is recommended).
5. When mounting to a cement floor, recommended mounting hardware is Great Lakes Seismic
Anchor Kit (AK101 or HDW-4-FLMT). For other floor construction, the installer must provide all
appropriate hardware.
8
DIAGRAM F
DIAGRAM G
Toe In: Rack depth MINUS 2.22"
Toe Out: Rack depth PLUS 2"
3/8-16 x 1" lg Hex
Head Bolt
3/8" Ext. Tooth Washer
3/8-16 Nut Plate
3/8" Ext. Tooth Washer
.75", Four
locations