ADEMCO 4021 Panduan Petunjuk Instalasi - Halaman 10
Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Sistem Keamanan ADEMCO 4021. ADEMCO 4021 15 halaman.
Standby: 3 cell Sealed Lead Acid Rechargeable Battery.
No. 1021's battery: 2.5 AH(Ademw No. 496)
No. 4021's battery: 2.5 AH (Ademw No. 494)
Standby time is dependent upon continuous load supplied to accessories, including smoke and combustion detectors,
and,,ff used, optional No. 5240 Remote Digital Keypads.
MAXIMUM STANDBY TlMES WliH VAhlOirS AUXILIARY AND SMOKE/COMBUSTION DETECTOR .
:'
,
CONTlNUOUS LOADS*
MA
0
50
100
150
200
250
300
350
400
HRS
100
32
18.5
13
9.5
7.5
6.5
5.5
4.5
I
ADDITIONAL TO PROCESSOR LOOP AND No. 5240 (ONE UNIT) CURRENTS.
* ADD 12 MA FOR EACH ADDITIONAL No. 5240 USED (IF ANY).
ADD 6 MA FOR EACH CUSTOM REMOTE PLATE USED (IF ANY).
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing by the user is vital
to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular maintenance program to the
user as well as s acquainting the user with the proper operation and limitations of the alarm system and its wm-
ponent parts. Recommendations must be included for a specific program of frequent testing (at least annually)
to insure the system's proper operation at all times.
-.-.
ALARM PROCESSING CENTER
..io21
-
4Il
ZONE
STATUS interior
TEST
FIRE
RESET
SYOSSET, N.Y. -
OFF
Diagram 2: No. 1021 RESIDENTIAL ALARM PROCESSING CENTER
467
459