Automated Logic R683 Petunjuk Teknis - Halaman 16
Jelajahi secara online atau unduh pdf Petunjuk Teknis untuk Unit Kontrol Automated Logic R683. Automated Logic R683 16 halaman. Rlm v4.7
Modstat page
CM 5 ($05)
HOA
Switches:
————
Power
Fails
00:00
Sun
System: EXEC 4.00
1
S01
3.0
(AHU4_1
FE,2
00:00
01/00/80
m n : F E
m l : 8 3 1 6
The following is an explanation of the Modstat page and
the messages that may appear there:
System: Beta 4.99.999 indicates the version of the
PROMs in the module, regardless of what you transfer
into it.
Revision: EEP400 3.4.118 is text from the EEP400 file.
It used to be a date, but now is a version number with a
date stamp embedded in it (3.2.813 is version 3.2 dated 8/
13).
Library: LIB400 3.4.118 is text from the LIB400 and is
a way of identifying what library was used to transfer the
module.
init:01 is the number of times that the module has reset
itself since the last power up.
wdt:0, 0 FF, 2 00:00 01/00/80 shows in order: the
number of times that the software watchdog timer has
gone off; the task number that was responsible; the lowest
value seen by the timer; the task responsible; and the
time and date of the last time that it went off.
al:00 is the module alarm bits (in hex).
halttime:10:00 is the halt timer. Normally at 10 minutes
when the module is not halted. Counts down when the
module is halted or has other serious errors. When it
reaches zero, the module re-initializes itself to try to clear
the source of the error.
hold:0 susp:0 are miscellaneous flags that should always
read zero.
badee:00 are error flags. Any non-zero value here will
have a "ERROR-Xxxxx" or "WARNING-Xxxxx" message
at the top of the screen to explain the nature of the error.
Rev. (30-JAN-98) • RLM v4.7
15:42 Wed 04/16/97
(123456—)OA
Temp:
INVALID
01/00/80,
00:00
Revision: EEP400 4.6
)
15
RLM
4.6
al:00
halttime:10:00
Type R683
at
65.00
Enthalpy:
Sun
01/00/80,
00:00
(CM05_1
)
Details:
hold:0
susp:0
yt:1498, 0E64.33 is the module time in hex. The format
is as follows: date, minutes, seconds, where "date" is the
number of days from Jan. 1, 1980, "minutes" is the
number of minutes since midnight last Sunday, and
"seconds" is seconds.
mn:FE is the "MaxNet." This applies when used with the
GCM.
ml:8212 is the "ModLoad," the start of the FB chain in
memory.
© 1995-98 Automated Logic Corporation
16
0.00
Sun
01/00/80
Library: LIB400
4.6
init:07
wdt:0,0
badee:00
yt:18AC,148E.2B